4–42 889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUALDEVICE CHAPTER 4: SETPOINTSIEC 60870-5-103 The point map for the 103 is different from the one shared by the IEC104 and DNPprotocols. IEC 60870-5-103 serial communications protocol is supported on the rear RS485port only.The DNP, 103 and Modbus can not be enabled simultaneously. Only one instance ofDNP3.0, IEC 103 or Modbus can run on the RS485 serial port.Path: Setpoints > Device > Communications > IEC60870-5-103• IEC103 Common ASDU Addrs• IEC103 Sync Timeout• IEC103 Activity TimeoutIEC103 Common ASDU AddrsRange: 0 to 254 in steps of 1Default: 0IEC103 Sync TimeoutRange: 0 to 1440 minutes in steps of 1 minDefault: 0 minIEC103 Activity TimeoutRange: 0 to 3600 seconds in steps of 1 sDefault: 0 sAll binary inputs are configured from FlexLogic operands. For a complete list, see FormatCode FC142.FASTPATH:The user must pay attention when configuring the function type and information numberof the different points, because they must be unique. There is no mechanism in theEnerVista 8 Series Setup software or the front panel HMI to detect duplication of theinformation index.FASTPATH:The IEC 60870-5-103 point lists always begin with point 0 and end at the first “Off” value.Since IEC 60870-5-103 point lists must be in one continuous block, any points assignedafter the first “Off” point are ignored.IEC 61850 The optional communications processor supports both the IEC61850 GOOSE and IEC61850 MMS Server service as per IEC 61850 standard Ed. 2. The GOOSE messaging serviceprovides the 889 unit the ability to Publish/Subscribe Digital Input Status and its Qualityand Timestamp to/from other IEDs with supporting GOOSE messaging service, while theserver support allows remote control center, RTU/Gateway, local HMI or other client roledevices access to the relay for monitoring and control. The configuration of IEC61850services is accomplished using the 889 configuration software, EnerVista 8 SeriesSetup software. A rebooting MUST be done before any changes made take affect.The IEC 61850 ConfiguratorThe 889 supports the IEC 61850 protocol which is identified by order code option “2E”.The IEC 61850 configurator is found in both the online and offline section of the EnerVista8 Series Setup software for configuring the online 889 and offline 889 settings filerespectively.Online and Offline SetupONLINE SETTINGS FILETwo options are available to configure the relay’s online settings file.1. Configuration