4–264 889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUALPROTECTION CHAPTER 4: SETPOINTSNOTENOTE:If the 3-phase VT uses a delta connection and FREQUENCY INPUT is set to Ph VT Bnk1-J2,the positive sequence voltage is used as the supervision voltage. In such condition, the truesupervision level is internally changed to 1/sqrt(3) of the user setting since the base of VThere is the phase-phase voltage.BLOCKRange: Off, Any FlexLogic operandDefault: OffOUTPUT RELAY XFor details see Common Setpoints.EVENTSRange: Enabled, DisabledDefault: EnabledTARGETSRange: Disabled, Self-reset, LatchedDefault: Self-reset