4–288 889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUALMONITORING CHAPTER 4: SETPOINTSCLOSE CIRCUIT MONITORINGPath: Setpoints > Monitoring > Breaker 1 > Close Circuit MonitoringFUNCTION:Range: Disabled, Latched Alarm, Alarm, ConfigurableDefault: DisabledPICKUP DELAY:Default: 10.000 sRange: 0.000 to 6000.000 s in steps of 0.001 sDROPOUT DELAY:Range: 0.000 to 6000.000 s in steps of 0.001 sDefault: 0.000 sBYPASS BREAKER STATE:Range: Enabled, DisabledDefault: DisabledSet the Bypass Breaker State to Enabled when a by-pass resistor is connected acrossthe breaker auxiliary contact for continuous Close circuit monitoring. The circuits aremonitored regardless of breaker position.BREAKER STATE OPENED:Range: Off, Any FlexLogic operand Contact inputs, Virtual inputs, Remote inputs.Default: OffThe setpoint selects the FlexLogic operand, digital input, virtual input or remote input toindicate that circuit breaker is opened. When the Bypass Breaker State is set to Disabled,monitoring of the close coil is blocked when the breaker is (not open) closed.OUTPUT RELAY XRange: Do Not Operate, OperateDefault: Do Not OperateBLOCK:Default: OffRange: Off, Any FlexLogic operandEVENTS:Range: Disabled, EnabledDefault: EnabledTARGETS:Range: Disabled, Self-reset, LatchedDefault: Self-reset