4–350 889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUALCONTROL CHAPTER 4: SETPOINTSBYPASS REM BLK CLOSERange: Off, Any FlexLogic operandDefault: OffThis setting specifies selection of an input which when asserted bypasses the assertedremote block close signal. Close command is permitted for the breaker.CLOSE SYNC SPVN BKRRange: Bypass, Sync 1 Cls PermDefault: order code dependant (e.g. Bypass or Sync 1Cls Perm)This setpoint selects whether or not the closing of the breaker is supervised by thesynchrocheck function. For this purpose the Synchrocheck element must be enabled.FASTPATH:If the supervision is not bypassed and Close is applied for an application where the breakeris located on radial feeders, or the line is powered by one source only, the DEAD SOURCEPERM setpoint from the Synchrocheck menu shall not be disabled.EVENTSRange: Disabled, EnabledDefault: EnabledTARGETSRange: Disabled, Self-reset, LatchedDefault: Self-reset