CHAPTER 4: SETPOINTS PROTECTION889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–243TD MULTIPLIERRange: 0.05 to 600.00 in steps of 0.01Default: 1.00This setting provides a selection for the Time Dial Multiplier which modifies the operatingtimes for the selected inverse curve. When the curve is set to “Definite Time”, T(s) = TDmultiplier. For example, setting the TD multiplier to 20 results in a time delay of 20seconds to operate when above the Volts/Hz pickup setting.T RESETRange: 0.00 to 6000.00 in steps of 0.01Default: 1.00Enter the time that the Volts per Hertz value must remain below the pickup level beforethe element resets.BLOCKRange: Off, FlexLogic OperandDefault: OffThe Volts per Hertz can be blocked by any asserted FlexLogic operand.OUTPUT RELAY XFor details see Common Setpoints.EVENTSRange: Enabled, DisabledDefault: EnabledTARGETSRange: Disabled, Self-reset, LatchedDefault: Self-reset