4–232 889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUALPROTECTION CHAPTER 4: SETPOINTSPICKUPRange: 0.00 to 3.00 x VT in steps of 0.01 x VTDefault: 1.50 x VTThis setting sets the auxiliary overvoltage pickup level specified per times VT.For example, a Pickup setting of 1.10 x VT with 13800:115 VT translates into 15.08kV (or126.5V secondary).CURVERange: Definite Time, Inverse Time, FlexCurves A/B/C/DDefault: Definite TimeThis setting provides the selection of curves for the overvoltage as definite time, inversetime overvoltage curves or FlexCurves.PICKUP DELAYRange: 0.000 - 6000.000s in steps of 0.001sDefault: 1.000sDROPOUT DELAYRange: 0.000 to 6000.000 s in steps of 0.001 sDefault: 1.000 sRESET RATERange: 0.000 to 6000.000 s in steps of 0.001 sDefault: 1.40 sThe reset rate is a linear reset time from the threshold of trip.BLOCKRange: Off, Any FlexLogic operandDefault: OffOUTPUT RELAY XFor details see Common Setpoints.EVENTSRange: Enabled, DisabledDefault: EnabledTARGETSRange: Disabled, Self-reset, LatchedDefault: Self-reset