4–258 889 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUALPROTECTION CHAPTER 4: SETPOINTSNEGATIVE VAR ALARM PICKUPRange: 0.02 to 2.00 x Rated in steps of 0.01Default: 0.85 x RatedThis setting specifies a pickup threshold for the negative var alarm function.POSITIVE VAR ALARM DELAYRange: 0.00 to 600.00 s in steps of 0.01 sDefault: 10.00 sThis setting specifies a time delay for the positive var alarm function.NEGATIVE VAR ALARM DELAYRange: 0.00 to 600.00 s in steps of 0.01 sDefault: 1.00 sThis setting specifies a time delay for the negative var alarm function.ALARM RELAY XFor details see Common Setpoints.BLOCK FROM ONLINERange: 0.00 to 600.00 s in steps of 0.01 sDefault: 0.50 sIn a generator application, it may be desirable not to trip or alarm on reactive poweruntil the machine is online and the field has been applied. Therefore, this feature can beblocked until the machine is online and adequate time has expired during which the fieldhad been applied. From that point forward, the reactive power trip and alarm elementswill be active. A value of zero for the block time indicates that the reactive powerprotection is active as soon as the generator comes online.BLOCKRange: Off, Any FlexLogic operandDefault: OffEVENTSRange: Disabled, EnabledDefault: DisabledTARGETSRange: Disabled, Self-reset, LatchedDefault: Self-reset