5.4 d: Reference SettingsYASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual 211Parameter Details5 d6-03: Field Forcing SelectionEnables or disables the Field Forcing function.Setting 0: DisabledSetting 1: Enabled d6-06: Field Forcing LimitSets the maximum level to what the Field Forcing function can boost the excitation current reference. The value is set asa percentage of the motor no load current.Note: Adjustment is not normally required. d7: Offset Frequency d7-01 to d7-03: Offset Frequency 1 to 3Three different offset values can be added to the frequency reference. They can be selected using digital inputsprogrammed for Offset frequency 1, 2, and 3 (H1- = 44, 45, 46). The selected offset values are added together ifmultiple inputs are closed at the same time. The value is set as a percentage of the Maximum Output Frequency.Note: This function can be used to replace the “Trim Control” function (H1- = 1C, 1D) of earlier YASKAWA drives.Figure 5.55 illustrates the Offset frequency function.Figure 5.55Figure 5.55 Offset Frequency OperationNo. Parameter Name Setting Range Defaultd6-03 Field Forcing Selection 0 or 1 0No. Parameter Name Setting Range Defaultd6-06 Field Forcing Limit 100 to 400% 400%No. Parameter Name Setting Range Defaultd7-01 Offset Frequency 1 -100.0 to 100.0% 0%d7-02 Offset Frequency 2 -100.0 to 100.0% 0%d7-03 Offset Frequency 3 -100.0 to 100.0% 0%FrequencyreferenceOffset Frequency 1 [d7-01](Signed)Offset Frequency 2 [d7-02](Signed)Offset Frequency 3 [d7-03](Signed)Multi-functioninput (44) = onMulti-functioninput (45) = onMulti-functioninput (46) = onSFS Frequencyreference aftersoft starter