B.3 Parameter TableYASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual 453Parameter ListBB.3 Parameter Table A: Initialization ParametersThe A parameter group creates the operating environment for the drive. This includes the parameter Access Level, MotorControl Method, Password, User Parameters and more. A1: Initialization ParametersNo.(Addr.) Name Description Setting PageA1-00(100H)<3><2> Default setting value is dependent on the Application Preset selected with parameter A1-06.<3> The parameter setting is not reset to the default value when A1-03 is used to initialize the drive.Language Selection0: English1: Japanese2: German3: French4: Italian5: Spanish6: Portuguese7: Chinese8: Czech9: Russian10: Turkish11: Polish12: GreekNote: 1. Settings 8 to 12 can be selected from an LCD operator with version (REV) F or later.The version is listed on the back of the LCD operator.2. The setting range is 0 to 7 in models CIMR-A4A0930 and 4A1200.Default: 0Min: 0Max: 12142A1-01(101H)<2>Access Level Selection 0: View and set A1-01 and A1-04. U- parameters can also be viewed.1: User Parameters (access to a set of parameters selected by the user, A2-01 to A2-32)2: Advanced Access (access to view and set all parameters)Default: 2Min: 0Max: 2142A1-02(102H)<3>Control Method Selection0: V/f Control1: V/f Control with PG2: Open Loop Vector Control3: Closed Loop Vector Control5: Open Loop Vector Control for PM6: Advanced Open Loop Vector Control for PM7: Closed Loop Vector Control for PMDefault: 0Min: 0Max: 7143A1-03(103H) Initialize Parameters0: No initialization1110: User Initialize (parameter values must be stored using parameter o2-03)2220: 2-wire initialization3330: 3-wire initialization5550: oPE04 error resetDefault: 0Min: 0Max: 5550143A1-04(104H) PasswordWhen the value set into A1-04 does not match the value set into A1-05, parameters A1-01through A1-03, A1-06, A1-07, and A2-01 through A2-32 cannot be changed.Default: 0000Min: 0000Max: 9999144A1-05(105H) Password SettingA1-06(127H) Application Preset0: General-purpose1: Water supply pump2: Conveyor3: Exhaust fan4: HVAC fan5: Air compressor6: Elevator7: HoistDefault: 0Min: 0Max: 7146A1-07(128H) DriveWorksEZ Function Selection 0: DWEZ disabled1: DWEZ enabled2: Digital input (enabled when H1- = 9F)Default: 0 Min: 0Max: 2147All ModesAll ModesAll ModesAll ModesAll ModesAll ModesAll Modes