5.5 E: Motor ParametersYASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual 223Parameter Details5 E5-01: Motor Code Selection (for PM Motors)If a YASKAWA motor that does not have a motor code or a PM motor from another company is used, set the parametersaccording to the motor nameplate values and test report values. Refer to Parameters that Change with the Motor CodeSelection (for PM Motors) on page 530 for details on the supported motor codes and their parameter settings.Setting parameter E5-01 to FFFF will allow to set the motor data manually using the E5- parameters.Note: 1. E5- parameters are not reset when the drive is initialized using parameter A1-03.2. When E5-01 is set to a value other than FFFF, the drive will not initialize using parameter A1-03.3. Changing E5-01 to FFFF from value other than FFFF will not change the values of parameters E5-02 through E5-24.4. Set E5-01 to FFFF when using a motor other than a YASKAWA SMRA, SSR1, or SST4 series.5. Default settings are:• OLV/PM, AOLV/PM: YASKAWA SSR1 Series (1750 min-1)• CLV/PM: YASKAWA SST4 Series (1750 min-1)6. Selection may vary depending on the motor code entered to E5-01.7. If an alarm or hunting occurs even though a motor code is used, enter the value indicated on the name plate. For details, refer toAuto-Tuning for Permanent Magnet Motors on page 121. E5-02: Motor Rated Power (for PM Motors)Sets the rated power of the motor. Determined by the value set to T2-04 during Stationary Auto-Tuning for PM motors orby entering the motor code to E5-01. E5-03: Motor Rated Current (for PM Motors)Sets the motor rated current in amps. This parameter is automatically set when the value is entered to T2-06 during theAuto-Tuning process.Note: Display is in the following units. CIMR-A2A0004 to 2A0040, CIMR-A4A0002 to 4A0023: 0.01 A units CIMR-A2A0056 to 2A0312, CIMR-A4A0031 to 4A0675: 0.1 A units CIMR-A4A0930 to 4A1200: 1 A units E5-04: Number of Motor Poles (for PM Motors)Sets the number of motor poles. This parameter is automatically set when the value is entered to T2-08 during theAuto-Tuning process. E5-05: Motor Stator Resistance (r1) (for PM Motors)Set the resistance for one motor phase. When measuring the resistance manually, make sure not to enter the line-to-lineresistance into E5-05. E5-06: Motor d-Axis Inductance (Ld) (for PM Motors)Sets the d-axis inductance in 0.01 mH units. This parameter is set during the Auto-Tuning process.No. Parameter Name Setting Range DefaultE5-01 Motor Code Selection (for PM Motors) 0000 to FFFF Determined by A1-02,C6-01 and o2-04No. Parameter Name Setting Range DefaultE5-02 Motor Rated Power (for PM Motors) 0.10 to 650.00 kW Determined by E5-01No. Parameter Name Setting Range DefaultE5-03 Motor Rated Current (for PM Motors) 10 to 200% of drive rated current Determined by E5-01No. Parameter Name Setting Range DefaultE5-04 Number of Motor Poles (for PM Motors) 2 to 48 Determined by E5-01No. Parameter Name Setting Range DefaultE5-05 Motor Stator Resistance (for PM Motors) 0.000 to 65.000 Determined by E5-01No. Parameter Name Setting Range DefaultE5-06 Motor d-Axis Inductance (for PM Motors) 0.00 to 300.00 mH Determined by E5-01