B.3 Parameter TableYASKAWA ELECTRIC SIEP C710616 27G YASKAWA AC Drive A1000 Technical Manual 507Parameter ListB q: DriveWorksEZ Parameters r: DriveWorksEZ Connection Parameters T: Motor TuningEnter data into the following parameters to tune the motor and drive for optimal performance T1: Induction Motor Auto-Tuningo4-07(523H)DC Bus Pre-Charge RelayMaintenance Setting Sets the point at which the cumulative timing for the soft charge bypass relay maintenancestarts. View monitor U4-06 to determine when the bypass relay may require replacement.Default: 0%Min: 0%Max: 150%319o4-09(525H) IGBT Maintenance Setting Sets the point at which the cumulative timing for the IGBTs maintenance starts.View monitor U4-07 to determine when the IGBTs may require replacement.Default: 0%Min: 0%Max: 150%319o4-11(510H) U2, U3 Initialization 0: U2- and U3- monitor data is not reset when the drive is initialized (A1-03).1: U2- and U3- monitor data is reset when the drive is initialized (A1-03). (The valueof o4-11 is automatically returned to 0.)Default: 0Min: 0Max: 1319o4-12(512H) kWh Monitor Initialization 0: U4-10 and U4-11 monitor data is not reset when the drive is initialized (A1-03).1: U4-10 and U4-11 monitor data is reset when the drive is initialized (A1-03). (The value ofo4-12 is automatically returned to 0.)Default: 0Min: 0Max: 1320o4-13(528H)Number of Run CommandsCounter Initialization 0: U4-02 monitor data is not reset when the drive is initialized (A1-03).1: U4-02 monitor data is reset when the drive is initialized (A1-03). (The value of o4-13 isautomatically returned to 0.)Default: 0Min: 0Max: 1320No. (Addr.) Name Description Setting Pageq1-01 toq6-07(1600H to1746H)DriveWorksEZ ParametersReserved for DriveWorksEZRefer to Help in theDWEZ software. 320No. (Addr.) Name Description Setting Pager1-01 tor1-40(1840H to1867H)DriveWorksEZ ConnectionParameters 1 to 20 (upper/lower) DriveWorksEZ Connection Parameters 1 to 20 (upper/lower)Default: 0Min: 0Max: FFFF320No. (Addr.) Name Description Setting PageT1-00(700H) Motor 1/Motor 2 Selection1: Motor 1 (sets E1-, E2-)2: Motor 2 (sets E3-, E4-)Default: 1Min: 1Max: 2127T1-01(701H)<37>Auto-Tuning Mode Selection0: Rotational Auto-Tuning1: Stationary Auto-Tuning 12: Stationary Auto-Tuning for Line-to-Line Resistance3: Rotational Auto-Tuning for V/f Control (necessary for Energy Savings and Speed EstimationSpeed Search)4: Stationary Auto-Tuning 25: Stationary Auto-Tuning 38: Inertia Tuning (perform Rotational Auto-Tuning prior to Inertia Tuning)9: ASR Gain Tuning (perform Rotational Auto-Tuning prior to ASR Gain Auto-Tuning)Note 1. Stationary Auto-Tuning 3 is not available in models CIMR-A4A0930 and 4A1200.2. Inertia Tuning and ASR Gain Auto-Tuning might not be available if gears are betweenthe machine and the motor shaft.Default: 0Min: 0Max: 4, 5, 8, 9 <10>128T1-02(702H) Motor Rated PowerSets the motor rated power as specified on the motor nameplate.Default: <9>Min: 0.00 kWMax: 650.00 kW128T1-03(703H) Motor Rated VoltageSets the motor rated voltage as specified on the motor nameplate.Default: 200.0 V <18>Min: 0.0 VMax: 255.0 V <18>128No. (Addr.) Name Description Setting PageAll ModesAll ModesAll ModesAll ModesAll ModesAll ModesAll ModesOLV/PM AOLV/PMCLVV/f w/PGCLV/PMV/f OLVOLV/PM AOLV/PMCLVV/f w/PGCLV/PMV/f OLVOLV/PM AOLV/PMCLVV/f w/PGCLV/PMV/f OLVOLV/PM AOLV/PMCLVV/f w/PGCLV/PMV/f OLV