7.2.5 SettingsPID-3492-SETTINGS v9Table 52:FUFSPVC Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / OnOpMode OffUNsINsUZsIZsUZsIZs ORUNsINsUZsIZs ANDUNsINsOptimZsNs- - UZsIZs Operating mode selection3U0> 1 - 100 %UB 1 30 Operate level of residual overvoltageelement in % of UBase3I0< 1 - 100 %IB 1 10 Operate level of residual undercurrentelement in % of IBase3U2> 1 - 100 %UB 1 30 Operate level of neg seq overvoltageelement in % of UBase3I2< 1 - 100 %IB 1 10 Operate level of neg seq undercurrentelement in % of IBaseOpDUDI OffOn- - Off Operation of change based functionOff/OnDU> 1 - 100 %UB 1 60 Operate level of change in phase voltagein % of UBaseDI< 1 - 100 %IB 1 15 Operate level of change in phase currentin % of IBaseUPh> 1 - 100 %UB 1 70 Operate level of phase voltage in % ofUBaseIPh> 1 - 100 %IB 1 10 Operate level of phase current in % ofIBaseSealIn OffOn- - On Seal in functionality Off/OnUSealln< 1 - 100 %UB 1 70 Operate level of seal-in phase voltage in% of UBaseIDLD< 1 - 100 %IB 1 5 Operate level for open phase currentdetection in % of IBaseUDLD< 1 - 100 %UB 1 60 Operate level for open phase voltagedetection in % of UBaseTable 53:FUFSPVC Non group settings (basic)Name Values (Range) Unit Step Default DescriptionGlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global BaseValue groups1MRK 511 424-UEN B Section 7Secondary system supervisionBay control REC650 2.2 IEC 117Technical manual