switches). The physical process in the switchyard is connected to these twofunction blocks via binary inputs and outputs.Four types of function blocks are available to cover most of the control andsupervision within the bay. These function blocks are interconnected to form acontrol function reflecting the switchyard configuration. The total number useddepends on the switchyard configuration. These types are:• Bay control QCBAY• Switch controller SCSWI• Circuit breaker SXCBR• Circuit switch SXSWIThe functions Local Remote (LOCREM) and Local Remote Control(LOCREMCTRL), to handle the local/remote switch. The functions Bay reserve(QCRSV) and Reservation input (RESIN), for the reservation function, also belongto the apparatus control function.The principles of operation, function blocks, input and output signals and settingparameters for all these functions are described below.8.3.3 Error handling GUID-6C31D291-74E8-46A3-8FC2-D3959C2458A5 v7Depending on the error that occurs during the command sequence the error signalwill be set with a value. Table 90 describes the cause values given on local HMI.The translation to AddCause values specified in IEC 61850-8-1 is shown in Table91. For IEC 61850-8-1 edition 2 only addcauses defined in the standard are used,for edition 1 also a number of vendor specific causes are used. The values areavailable in the command response to commands from IE C61850-8-1 clients. Anoutput L_CAUSE on the function block for Switch controller (SCSWI), Circuitbreaker (SXCBR) and Circuit switch (SXSWI) indicates the value of the causeduring the latest command if the function specific command evaluation has beenstarted. The causes that are not always reflected on the output L_CAUSE, withdescription of the typical reason are listed in table 92.Table 90:Values for "cause" signalCausenumberName Description Supported0 None Control action successfully executed X1 Not-supported Given for Cancel request with Direct Control in ReadystateX2 Blocked-by-switching-hierarchyNot successful since one of the downstream Locswitches like in CSWI has the value TRUEX3 Select-failed Cancelled due to an unsuccessful selection (selectservice)X4 Invalid-position Control action is aborted due to invalid switch position(Pos in XCBR or XSWI)X5 Position-reached Switch is already in the intended position (Pos inXCBR or XSWI)XTable continues on next page1MRK 511 424-UEN B Section 8ControlBay control REC650 2.2 IEC 209Technical manual