PID-6951-INPUTSIGNALS v7Table 316:SSIML Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of functionBLKALM BOOLEAN 0 Block all the alarmsSENLEVEL REAL 0.0 Level input from CBSENTEMP REAL 0.0 Temperature of the insulation medium from CBSENLVLALM BOOLEAN 0 Level alarm signalSENLVLLO BOOLEAN 0 Level lockout signalSETLLO BOOLEAN 0 Set level lockoutSETTLO BOOLEAN 0 Set temperature lockoutRESETLO BOOLEAN 0 Reset level and temperature lockoutPID-6951-OUTPUTSIGNALS v7Table 317:SSIML Output signalsName Type DescriptionLOCKOUT BOOLEAN Level below lockout level or temperature abovelockout levelLVLLO BOOLEAN Level below lockout levelTEMPLO BOOLEAN Temperature above lockout levelALARM BOOLEAN Level below alarm level or temperature abovealarm levelLVLALM BOOLEAN Level below alarm levelTEMPALM BOOLEAN Temperature above alarm levelLEVEL REAL Level service valueTEMP REAL Temperature of the insulation medium10.3.5 SettingsPID-6951-SETTINGS v7Table 318:SSIML Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / OnLevelAlmLimit 1.00 - 100.00 - 0.01 5.00 Alarm setting for levelLevelLOLimit 1.00 - 100.00 - 0.01 3.00 Level lockout settingTempAlarmLimit -40.00 - 200.00 - 0.01 30.00 Temperature alarm level setting of themediumTempLOLimit -40.00 - 200.00 - 0.01 30.00 Temperature lockout level of the mediumtLevelAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for level alarmtLevelLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for level lockout indicationtTempAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for temperature alarmTable continues on next page1MRK 511 424-UEN B Section 10MonitoringBay control REC650 2.2 IEC 391Technical manual