• Blocking of position indications, BL_UPD. This input will block all inputsrelated to apparatus positions for all configured functions within the bay.• Blocking of commands, BL_CMD. This input will block all commands for allconfigured functions within the bay.The switching of the Local/Remote switch requires at least system operator level.The password will be requested at an attempt to operate if authority levels havebeen defined in the IED, otherwise the default authority level can handle thecontrol without LogOn. The users and passwords are defined with the IED Userstool in PCM600.8.3.5 Local/Remote switch LOCREM IP16319-1 v3M17086-3 v10The signals from the local HMI or from an external local/remote switch areconnected via the function blocks local remote (LOCREM) and local remotecontrol (LOCREMCTRL) to the Bay control (QCBAY) function block. Theparameter ControlMode in function block LOCREM is set to choose if the switchsignals are coming from the local HMI or from an external hardware switchconnected via binary inputs.8.3.5.1 Function block M17088-3 v4LOCREMCTRLOFFLOCCTRLREMCTRLLHMICTRLOFFLOCALREMOTEVALIDIEC05000360-3-en.vsdxIEC05000360 V3 EN-USFigure 87: LOCREM function blockLOCREMCTRL^PSTO1^PSTO2^PSTO3^PSTO4^PSTO5^PSTO6^PSTO7^PSTO8^PSTO9^PSTO10^PSTO11^PSTO12HMICTR1HMICTR2HMICTR3HMICTR4HMICTR5HMICTR6HMICTR7HMICTR8HMICTR9HMICTR10HMICTR11HMICTR12IEC05000361-3-en.vsdxIEC05000361 V3 EN-USFigure 88: LOCREMCTRL function blockSection 8 1MRK 511 424-UEN BControl216 Bay control REC650 2.2 IECTechnical manual