13.3.6.4 Settings SEMOD55954-1 v2PID-6753-SETTINGS v1Table 390:MVGAPC Non group settings (basic)Name Values (Range) Unit Step Default DescriptionBasePrefix micromilliunitkiloMegaGigaTera- - unit Base prefix (multiplication factor)MV db 1 - 100000 Type 1 10000 Cycl: Report interval (s), Db: In % ofrange, Int Db: In %sMV zeroDb 0 - 100000 m% 500 1000 Zero point clamping in 0,001% of rangeMV hhLim -5000.00 - 5000.00 xBase 0.01 900.00 High High limit multiplied with the baseprefix (multiplication factor)MV hLim -5000.00 - 5000.00 xBase 0.01 800.00 High limit multiplied with the base prefix(multiplication factor)MV lLim -5000.00 - 5000.00 xBase 0.01 -800.00 Low limit multiplied with the base prefix(multiplication factor)MV llLim -5000.00 - 5000.00 xBase 0.01 -900.00 Low Low limit multiplied with the baseprefix (multiplication factor)MV min -5000.00 - 5000.00 xBase 0.01 -1000.00 Minimum value multiplied with the baseprefix (multiplication factor)MV max -5000.00 - 5000.00 xBase 0.01 1000.00 Maximum value multiplied with the baseprefix (multiplication factor)MV dbType CyclicDeadbandInt deadbandDb & Cyclic 5sDb & Cyclic 30sDb & Cyclic 1min- - Deadband Reporting typeMV limHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (commonfor all limits)13.3.6.5 Monitored dataPID-6753-MONITOREDDATA v1Table 391:MVGAPC Monitored dataName Type Values (Range) Unit DescriptionVALUE REAL - - Magnitude of deadbandvalueRANGE INTEGER 1=High2=Low3=High-High4=Low-Low0=Normal- RangeSection 13 1MRK 511 424-UEN BStation communication494 Bay control REC650 2.2 IECTechnical manual