Name of OUTx Type Description Value whenactivatedValue whendeactivatedOUT11 BOOLEAN Output 11 1024 0OUT12 BOOLEAN Output 12 2048 0OUT13 BOOLEAN Output 13 4096 0OUT14 BOOLEAN Output 14 8192 0OUT15 BOOLEAN Output 15 16384 0OUT16 BOOLEAN Output 16 32768 0The sum of the numbers in column “Value when activated” when all OUTx(1≤x≤16) are active equals 65535. This is the highest integer that can be convertedto boolean by the ITBGAPC function block.The operator position input (PSTO) determines the operator place. The integernumber that is communicated to the ITBGAPC can only be written to the blockwhile the PSTO is in position “Remote”. If PSTO is in position ”Off” or ”Local”,then no changes are applied to the outputs.9.14.7 Technical dataGUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2Table 260:Number of ITBGAPC instancesFunction Quantity with cycle time3 ms 8 ms 100 msITBGAPC 4 4 89.15 Elapsed time integrator with limit transgression andoverflow supervision TEIGAPC9.15.1 Identification GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3Function Description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2 devicenumberElapsed time integrator TEIGAPC - -9.15.2 Functionality GUID-390D7433-0C1C-48B4-9A90-71AA148C3C35 v3Elapsed Time Integrator (TEIGAPC) function is a function that accumulates theelapsed time when a given binary signal has been high, see also Figure 165.Section 9 1MRK 511 424-UEN BLogic340 Bay control REC650 2.2 IECTechnical manual