Data Value Data Valid Comm Valid TestReceiver in test mode and incomingdata with q= NormalUpdated 1 1 0Receiver in test mode and incomingdata with q= TestUpdated 1 1 1Communication Error 0 0 0 0The input of this GOOSE block must be linked either in SMT bymeans of a cross or in ACT by means of a GOOSE connection (ifeasy GOOSE engineering is enabled) to receive the double pointvalues.The implementation for IEC 61850 quality data handling isrestricted to a simple level. If quality data validity is GOOD thenthe DATAVALID output will be HIGH. If quality data validity isINVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLDDATA then the DATAVALID output will be LOW.13.3.8 GOOSE function block to receive an integer valueGOOSEINTRCV13.3.8.1 IdentificationGUID-93A1E81B-1DE8-483A-BB3B-DB771EE66DC1 v1Function description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberGOOSE function block to receive aninteger valueGOOSEINTRCV - -13.3.8.2 Functionality GUID-27B1ED7A-C8E8-499E-89C1-C656FB0337F8 v3GOOSEINTRCV is used to receive an integer value using IEC 61850 protocol viaGOOSE.13.3.8.3 Function block GUID-56F0C9F7-98F3-4091-B071-53CA5074DC8F v1IEC10000250-2-en.vsdGOOSEINTRCVBLOCK^SRCINTOUT^INTOUTDATAVALIDCOMMVALIDTESTIEC10000250 V2 EN-USFigure 238: GOOSEINTRCV function block1MRK 511 424-UEN B Section 13Station communicationBay control REC650 2.2 IEC 497Technical manual