with no priority. If the control model used is Select before operate,Also the corresponding enable input must be set, and nointerlocking is active. The L_SEL input must be set beforeL_OPEN or L_CLOSE is operated, if the control model is Selectbefore operate.If one multi-phase XCBR/XSWI or two single-phase XCBR/XSWIare used for a two- or three-phase system, two or more of the inputsXPOSL1, XPOSL2 and XPOSL3 are connected to the same source.8.3.6.4 SettingsPID-6798-SETTINGS v4Table 104:SCSWI Non group settings (basic)Name Values (Range) Unit Step Default DescriptionCtlModel Dir NormSBO Enh- - SBO Enh Specifies control model typePosDependent Always permittedNot perm at 00/11- - Always permitted Permission to operate depending on thepositiontSelect 0.00 - 600.00 s 0.01 30.00 Maximum time between select andexecute signalstResResponse 0.000 - 60.000 s 0.001 5.000 Allowed time from reservation request toreservation grantedtSynchrocheck 0.00 - 600.00 s 0.01 10.00 Allowed time for synchrocheck to fulfilclose conditionstSynchronizing 0.00 - 600.00 s 0.01 0.00 Supervision time to get the signalsynchronizing in progresstExecutionFB 0.00 - 600.00 s 0.01 30.00 Maximum time from command executionto terminationtPoleDiscord 0.000 - 60.000 s 0.001 2.000 Allowed time to have discrepancybetween the polesSuppressMidPos OffOn- - On Mid-position is suppressed during timetIntermediate; tIntermediate is set oneach connected XCBR/XSWI functionindividuallyInterlockChk Sel & Op phaseOp phase- - Sel & Op phase Selection if interlock check should bedone in select phase8.3.6.5 Operation principleM13484-4 v4The Switch controller (SCSWI) is provided with verification checks for the select -execute sequence, that is, checks the conditions prior each step of the operation arefulfilled. The involved functions for these condition verifications are interlocking,reservation, blockings and synchrocheck.Control handling M13484-6 v7.Section 8 1MRK 511 424-UEN BControl222 Bay control REC650 2.2 IECTechnical manual