9.14.5 SettingsGUID-F573CA16-4821-4203-970A-F7D01AF5E63B v1This function does not have any setting parameters.9.14.6 Operation principle SEMOD176587-4 v6An example is used to explain the principle of operation: With integer 15 sent toand received by the ITBGAPC function on the IEC 61850 the OUTx changes from0 to 1 on each of the OUT1; OUT2 OUT3 and OUT4. All other OUTx (5≤x≤16)remains 0. The boolean interpretation of this is represented by the assigned valuesof each of the outputs OUT1 = 1; and OUT2 = 2; and OUT3= 4; and OUT4 = 8.The sum of these OUTx (1≤x≤4) is equal to the integer 15 received via the IEC61850 network. The remaining OUTx = 0 for (5≤x≤16).OUTx represents a value when activated. The value of each of the OUTx is inaccordance with the Table 259. When not activated the OUTx has the value 0.The value of each OUTx for 1≤x≤16 (1≤x≤16) follows the general formulae:OUTx = 2x-1 The sum of the values of all activated OUTx = 2x-1 where 1≤x≤16will be equal to the integer value received over IEC 61850 to the ITBGAPC_1function block.The Integer to Boolean 16 conversion with logic node representation function(ITBGAPC) will transfer an integer with a value between 0 to 65535communicated via IEC 61850 and connected to the ITBGAPC function block to acombination of activated outputs OUTx where 1≤x≤16. The values represented bythe different OUTx are according to Table 259. When an OUTx is not activated, itsvalue is 0.The ITBGAPC function is designed for receiving the integer input from a stationcomputer - for example, over IEC 61850. If the BLOCK input is activated, it willfreeze the logical outputs at the last value.Table 259:Outputs and their values when activatedName of OUTx Type Description Value whenactivatedValue whendeactivatedOUT1 BOOLEAN Output 1 1 0OUT2 BOOLEAN Output 2 2 0OUT3 BOOLEAN Output 3 4 0OUT4 BOOLEAN Output 4 8 0OUT5 BOOLEAN Output 5 16 0OUT6 BOOLEAN Output 6 32 0OUT7 BOOLEAN Output 7 64 0OUT8 BOOLEAN Output 8 128 0OUT9 BOOLEAN Output 9 256 0OUT10 BOOLEAN Output 10 512 0Table continues on next page1MRK 511 424-UEN B Section 9LogicBay control REC650 2.2 IEC 339Technical manual