11.1.4 SignalsPID-6509-INPUTSIGNALS v4Table 359:PCFCNT Input signalsName Type Default DescriptionBI_PULSE BOOLEAN 0 Connect binary input channel for meteringBLOCK BOOLEAN 0 Block of functionREAD_VAL BOOLEAN 0 Initiates an additional pulse counter readingRS_CNT BOOLEAN 0 Resets pulse counter valuePID-6509-OUTPUTSIGNALS v4Table 360:PCFCNT Output signalsName Type DescriptionINVALID BOOLEAN The pulse counter value is invalidRESTART BOOLEAN The reported value does not comprise a completeintegration cycleBLOCKED BOOLEAN The pulse counter function is blockedNEW_VAL BOOLEAN A new pulse counter value is generatedSCAL_VAL REAL Scaled value with time and status information11.1.5 SettingsPID-6509-SETTINGS v4Table 361:PCFCNT Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/OnEventMask NoEventsReportEvents- - NoEvents Report mask for analog events frompulse counterCountCriteria OffRisingEdgeFalling edgeOnChange- - RisingEdge Pulse counter criteriaScale 1.000 - 90000.000 - 0.001 1.000 Scaling value for SCAL_VAL output tounit per counted valueQuantity CountActivePowerApparentPowerReactivePowerActiveEnergyApparentEnergyReactiveEnergy- - Count Measured quantity for SCAL_VAL outputtReporting 0 - 3600 s 1 60 Cycle time for reporting of counter valueSection 11 1MRK 511 424-UEN BMetering460 Bay control REC650 2.2 IECTechnical manual