Name Type DescriptionOUT9 BOOLEAN Binary output 9DVALID9 BOOLEAN Valid data on binary output 9OUT10 BOOLEAN Binary output 10DVALID10 BOOLEAN Valid data on binary output 10OUT11 BOOLEAN Binary output 11DVALID11 BOOLEAN Valid data on binary output 11OUT12 BOOLEAN Binary output 12DVALID12 BOOLEAN Valid data on binary output 12OUT13 BOOLEAN Binary output 13DVALID13 BOOLEAN Valid data on binary output 13OUT14 BOOLEAN Binary output 14DVALID14 BOOLEAN Valid data on binary output 14OUT15 BOOLEAN Binary output 15DVALID15 BOOLEAN Valid data on binary output 15OUT16 BOOLEAN Binary output 16DVALID16 BOOLEAN Valid data on binary output 16COMMVALID BOOLEAN Communication ValidTEST BOOLEAN Test Output13.3.12.3 Settings SEMOD173168-1 v2PID-6827-SETTINGS v3Table 409:GOOSEBINRCV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/On13.3.12.4 Operation principle GUID-950F2501-9183-43C0-A193-7D15124F6CCE v1The DVALIDx output will be HIGH if the incoming message is with valid data.The COMMVALID output will become LOW when the sending IED is under totalfailure condition and the GOOSE transmission from the sending IED does nothappen.The TEST output will go HIGH if the sending IED is in test mode.Data Value Data Valid Comm Valid TestIncoming data with q=Normal Updated 1 1 0Incoming data with q=oldData 0 0 1 0Incoming data with q=Invalid 0 0 1 0Incoming data with q=test 0 0 1 1Table continues on next pageSection 13 1MRK 511 424-UEN BStation communication510 Bay control REC650 2.2 IECTechnical manual