8 SmartWire-DT8.10 SmartWire-DT diagnostics214 DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com8.10.4 SmartWire-DT diagnostic LEDsThe following table shows the information that can be determined based onthe SmartWire-DT diagnostic LEDs.Table 44: SmartWire-DT diagnostic LED indicationsSwitching command presentFor the orange SmartWire-DT diagnostic LED, the “switching commandpresent” message means the following:• Profiles 1, 2, 3: DS7 Start/Stop = 1.• Profiles 4, 5, 6, 10:EN_Set and EN_Op = 1.• Profiles 7, 8, 9, 11:OnOff =1, Off2 =1, Off3 = 1, EN_Op = 1,EN_Ramp = 1, Freeze = 1, EN_Set = 1, Ctl_PLC = 1.DiagnosticsIf the “Diagnostics” message appears, input byte 0, bit 4 (DIAG) will be setto 1 as well. The message has the following meaning:• Profiles 1 to 9: There is an advanced diagnostic alarm for soft starter DS7or motor-protective circuit-breaker PKE.• Profiles 10 and 11: There is an advanced diagnostic message for theDS7-SWD soft starterColor LED SwitchcommandPosition1-0-A switchStatus Status signal– – – off No power supplyOrange Available A Continuous light Device is operating error-free.flashing (3 Hz) DiagnosticsGreen not available 1 or0 orAContinuous light Device is operating error-free.flashing (1 Hz) • addressing process in progress• After powering on the gateway• After pressing the configuration button on the gateway• Module not present in current configuration• invalid typeflashing (3 Hz) Diagnostics