2 Engineering2.9 DS7-SWD and PKE motor-protective circuit-breakersDS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 392.9 DS7-SWD and PKE motor-protective circuit-breakersDS7-SWD soft starters can also provide the following functions when usedtogether with a PKE motor-protective circuit-breaker:• Protecting the DS7 soft starter against overload• adjustable current limitation,• ZMR overload relay function (in the event of an overload, the DS7 softstarter will switch off the load, instead of the PKE motor-protectivecircuit-breaker doing so)• Currents readable via SmartWire-DT→ After a motor protective device has tripped, the soft starter andthe protective device cannot be switched on again until it hascooled down. The reset depends on the temperature.Figure 21: Motor-starter combination: DS7-SWD and PKE→ Only PKE trip blocks (PKE-XTUWA-32, PKE-XTUA-…) should beused for motor protection in combination with DS7 soft starters.PKE trip block PKE-XTUCP-… for system protection must not beused in combination with a soft starter DS7! In combinationwith SmartWire-DT this can cause false tripping.M3 ~1L13L25L32T14T26T3L1L2L3PEQ1Q21BG1, BG2M1I > I > I >SWD4-8SF2-5+ 15V