3 Installation3.3 Flush mounting in control panelDS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 693.3.2 Mounting instructions (BG 1 and BG 2)3.3.2.1 Free surrounding areas→ An installation clearance of 25 mm must be maintained in frontof size 1 and size 2 (up to 32 A) DS7 soft starters. A top andbottom clearance of 75 mm each is required. If the clearancesare smaller, derating will be necessary or it will be necessary touse the optional DS7-FAN-032 fan.All sizes can be mounted directly next to each other.Side clearance is not required to other devices that do notthemselves require clearance at the sides.Figure 50: Installation clearances for devices up to 32 ATop: Devices without SmartWire-DT; bottom: Devices withSmartWire-DT→ If the point if installation is subject to continuous vibration orshocks, design measures must be taken for dampening, such asthrough the use of vibration dampers.≧ 25 mm(≧ 0.98")≧ 0 ≧ 0≧ 75 mm(≧ 2.95")≧ 75 mm(≧ 2.95")≧ 25 mm(≧ 0.98")