1 Device series DS71.7 Technical dataDS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 211.7.2 General dataTable 6: General Technical DataGeneralProduct standard IEC/EN 60 947-4-2Approvals, certificates CE, UL, CSA, CCC, GostMounting position verticalDegree of protection IP20 for the front and operator control and operatingelements.IP20 on all sides in size 1IP00 on all sides in size 2, 3, 4Busbar tag shroud Finger- and back-of-hand proofMechanical shock resistance 8 g/11 msVibration resistance to EN 60721-3-2 2M2Power sectionRated operating voltage 200 - 480 V AC ±10 %Mains frequency 50/60 Hz ±5 %Overload cycle to EN 60947-4-2 AC53a: 3-5: 75-10Minimum load current 0.5 ARated impulse withstand voltageU imp 1.2/50 μs4 kVRated insulation voltage U i 500 VOvervoltage category/pollution degree II/2Control section (inclusive SmartWire-DT)Supply-/control voltage depending on variant24 V AC / 24 V DC (18 - 30 V ± 0 %)120 - 230 V AC (98 - 264 V ± 0 %)Mains frequency (with AC versions) 50/60 Hz ±5 %Rated impulse withstand voltage U imp 2.5 kVRated insulation voltage U i 300 VOver voltage category IISoft start functionsRamp timesAcceleration 1 - 30 sLag 0 (= free run-down), 1 - 30 sStart voltage (= switch-off voltage) 30 - 100 %Controlling and signallingControl inputs depending on variant2 with size 14 with size 25 with size 3, size 4Relay depending on variant1 with size 1 (non-isolated)2 with size 2, 3, 4 (potential-free)LED 2 at DS7 without SWD (DS7-340…, DS7-342…)3 at DS7 without SWD (DS7-34D…)