CHAPTER 2: MODBUS COMMUNICATION MEMORY MAPUR FAMILY – COMMUNICATIONS GUIDE 2-812" 6151 Transformer Aging Factor Pickup 1 to 10 PU 0.1 F001 20" 6152 Transformer Aging Factor Delay 0 to 30000 min 1 F001 10" 6153 Transformer Aging Factor Block 0 to 4294967295 --- 1 F300 0" 6155 Transformer Aging Factor Target 0 to 2 --- 1 F109 0 (Self-reset)" 6156 Transformer Aging Factor Events 0 to 1 --- 1 F102 0 (Disabled)Transformer Loss of Life (Read/Write Grouped Setting)G30, T35, T60 6160 Transformer Loss of Life Function 0 to 1 --- 1 F102 0 (Disabled)" 6161 XFMR LOL Initial Value 0 to 500000 hrs 1 F003 0" 6163 Transformer Loss of Life Pickup 0 to 500000 hrs 1 F003 180000" 6165 Transformer Loss Of Life Block 0 to 4294967295 --- 1 F300 0" 6167 Transformer Loss of Life Target 0 to 2 --- 1 F109 0 (Self-reset)" 6168 Transformer Loss of Life Events 0 to 1 --- 1 F102 0 (Disabled)Transformer Thermal Inputs (Read/Write Setting)G30, T35, T60 6170 Transformer Thermal Model Source Input 0 to 5 --- 1 F167 0 (SRC 1)" 6171 Ambient Temperature Input Sensor 0 to 32 --- 1 F450 0" 6172 Top Oil Temperature Input Sensor 0 to 32 --- 1 F460 0" 6173 January Average Ambient Temperature -60 to 60 °C 1 F002 -20" 6174 February Average Ambient Temperature -60 to 60 °C 1 F002 -30" 6175 March Average Ambient Temperature -60 to 60 °C 1 F002 -10" 6176 April Average Ambient Temperature -60 to 60 °C 1 F002 10" 6177 May Average Ambient Temperature -60 to 60 °C 1 F002 20" 6178 June Average Ambient Temperature -60 to 60 °C 1 F002 30" 6179 July Average Ambient Temperature -60 to 60 °C 1 F002 30" 617A August Average Ambient Temperature -60 to 60 °C 1 F002 30" 617B September Average Ambient Temperature -60 to 60 °C 1 F002 20" 617C October Average Ambient Temperature -60 to 60 °C 1 F002 10" 617D November Average Ambient Temperature -60 to 60 °C 1 F002 10" 617E December Average Ambient Temperature -60 to 60 °C 1 F002 -10Transformer Thermal Inputs (Read/Write Command)G30, T35, T60 6180 Transformer Loss of Life Clear Command 0 to 1 --- 1 F126 0 (No)Transformer Percent Differential (Read/Write Grouped Setting)G30, T35, T60 61C0 Percent Differential Function 0 to 1 --- 1 F102 0 (Disabled)" 61C1 Percent Differential Pickup 0.05 to 1 pu 0.001 F001 100" 61C2 Percent Differential Slope 1 15 to 100 % 1 F001 25" 61C3 Percent Differential Break 1 1 to 2 pu 0.001 F001 2000" 61C4 Percent Differential Break 2 2 to 30 pu 0.001 F001 8000" 61C5 Percent Differential Slope 2 50 to 100 % 1 F001 90" 61C6 Inrush Inhibit Function 0 to 2 --- 1 F168 1 (Adapt.2nd)" 61C7 Inrush Inhibit Level 1 to 40 %fo 0.1 F001 200" 61C8 Overexcitation Inhibit Function 0 to 1 --- 1 F169 0 (Disabled)" 61C9 Overexcitation Inhibit Level 1 to 40 %fo 0.1 F001 100" 61CA Percent Differential Block 0 to 4294967295 --- 1 F300 0" 61CC Percent Differential Target 0 to 2 --- 1 F109 0 (Self-reset)" 61CD Percent Differential Events 0 to 1 --- 1 F102 0 (Disabled)" 61CE Transformer Inrush Inhibit Mode 0 to 3 --- 1 F189 0 (Per phase)Products Address Register name Range Units Step Format Default