3-100 UR FAMILY – COMMUNICATIONS GUIDEMODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION3Table 3-114: Sensitive directional power stage 1 data objectsTable 3-115: Sensitive directional power stage 2 data objects3.5.2.68 Speed 2 motor acceleration time (S2AcTm)This element is instantiated in the following products: M60.Table 3-116: Speed 2 acceleration time data objectsLNName: Sen1PDOP# LDevice inst: Prot UR element: Sensitive Directional Power element # stage 1 functionsdata obj. data attribute Type FC UR Name Description R/W/CStr ACD DIR POWER # STG1 PKP operand, whichbecomes On when the directional powercomparator has operated.Rgeneral BOOLEAN ST DIR POWER # STG1 PKP RdirGeneral ENUMERATED ST 0, the code for unknown. It is unknown asthe element may be connected/configured to look forward or backwardROp ACT DIR POWER # STG1 OP operand Rgeneral BOOLEAN ST DIR POWER # STG1 OP RDpo SPS DIR POWER # STG1 DPO operand, whichis the inverse of DIR POWER STG1 OPRstVal BOOLEAN ST DIR POWER # STG1 DPO RLNName: Sen2PDOP# LDevice inst: Prot UR element: Sensitive Directional Power element # stage 2 functionsdata obj. data attribute Type FC UR Name Description R/W/CStr ACD DIR POWER # STG2 PKP operand, whichbecomes On when the directional powercomparator has operated.Rgeneral BOOLEAN ST DIR POWER # STG2 PKP RdirGeneral ENUMERATED ST 0, the code for unknown. It is unknown asthe element may be connected/configured to look forward or backwardROp ACT DIR POWER # STG2 OP operand Rgeneral BOOLEAN ST DIR POWER # STG2 OP RDpo SPS DIR POWER # STG2 DPO operand, whichis the inverse of DIR POWER STG2 OPRstVal BOOLEAN ST DIR POWER # STG2 DPO RLNName: S2AcTmPMSS1 LDevice inst: Prot UR element: SPEED2 Acceleration Time elementdata obj. data attribute Type FC UR Name Description R/W/CMod INC This logical node’s mode R/CtrlstVal ENUMERATED ST 1 (on) RctlModel CtlModels CF 0 (status only) RHealth INS This logical node’s health RstVal ENUMERATED ST LPHD1.PhyHealth.stVal ROp ACT MOTOR SPD2 ACL t OP operand Rgeneral BOOLEAN ST MOTOR SPD2 ACL t OP RDpo SPS MOTOR SPD2 ACL t DPO operand RstVal BOOLEAN ST MOTOR SPD2 ACL t DPO RSPDTR SPS MOTOR SPD2 TR 2-1 OP operand RstVal BOOLEAN ST MOTOR SPD2 TR 2-1 OP RBlkRefγ ORG SPEED2 ACCEL BLOCK setting for settinggroup γ.RGEORG RsetSrcRef ObjectReference SP SPEED2 ACCEL BLOCK. reference to the data attribute to input R/CVISIBLESTRING255SP Reference to the ultimate sourceof value selected by settingSPEED2 ACCEL BLOCK.R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C