2-104 UR FAMILY – COMMUNICATIONS GUIDEMEMORY MAP CHAPTER 2: MODBUS COMMUNICATION2" 70A2 ...Repeated for Breaker Failure 19" 70AB ...Repeated for Breaker Failure 20" 70B4 ...Repeated for Breaker Failure 21" 70BD ...Repeated for Breaker Failure 22" 70C6 ...Repeated for Breaker Failure 23" 70CF ...Repeated for Breaker Failure 24Phase Undervoltage (Read/Write Grouped Setting) (3 Modules)All except B90,C30, T357000 Phase Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)" 7001 Phase Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)" 7002 Phase Undervoltage 1 Pickup 0.004 to 3 pu 0.001 F001 1000" 7003 Phase Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (DefiniteTime)" 7004 Phase Undervoltage 1 Delay 0 to 600 s 0.01 F001 100" 7005 Phase Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100" 7006 Phase Undervoltage 1 Block 0 to 4294967295 --- 1 F300 0" 7008 Phase Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)" 7009 Phase Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)" 700A Phase Undervoltage 1 Measurement Mode 0 to 1 --- 1 F186 0 (Phase toGround)" 700B Reserved (6 items) 0 to 1 --- 1 F001 0" 7013 ...Repeated for Phase Undervoltage 2" 7022 ...Repeated for Phase Undervoltage 3Phase Overvoltage (Read/Write Grouped Setting) (3 Modules)B30, C60, C70,D30, D60, F35,F60, G30, G60,L30, L60, L90,M60, N60, T607040 Phase Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)" 7041 Phase Overvoltage 1 Source 0 to 5 --- 1 F167 0 (SRC 1)" 7042 Phase Overvoltage 1 Pickup 0.004 to 3 pu 0.001 F001 1000" 7043 Phase Overvoltage 1 Delay 0 to 600 s 0.01 F001 100" 7044 Phase Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100" 7045 Phase Overvoltage 1 Block 0 to 4294967295 --- 1 F300 0" 7047 Phase Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)" 7048 Phase Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)" 7049 ...Repeated for Phase Overvoltage 2" 7052 ...Repeated for Phase Overvoltage 3Phase Distance (Read/Write Grouped Setting) (3 or 5 Modules)D30, D60, G60,L60, L90, T607070 Phase Distance Zone 1 Function 0 to 1 --- 1 F102 0 (Disabled)" 7071 Phase Distance Zone 1 Current Supervision 0.05 to 30 pu 0.001 F001 200" 7072 Phase Distance Zone 1 Reach 0.02 to 500 ohms 0.01 F001 200" 7073 Phase Distance Zone 1 Direction 0 to 2 --- 1 F154 0 (Forward)" 7074 Phase Distance Zone 1 Comparator Limit 30 to 90 degrees 1 F001 90" 7075 Phase Distance Zone 1 Delay 0 to 65.535 s 0.001 F001 0" 7076 Phase Distance Zone 1 Block 0 to 4294967295 --- 1 F300 0" 7078 Phase Distance Zone 1 Target 0 to 2 --- 1 F109 0 (Self-reset)" 7079 Phase Distance Zone 1 Events 0 to 1 --- 1 F102 0 (Disabled)Products Address Register name Range Units Step Format Default