3-124 UR FAMILY – COMMUNICATIONS GUIDEMODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION33.5.3.10 Cold load pickup (Cold)This element is instantiated in the following products: F35, F60.Table 3-146: Cold load pickup data objects3.5.3.11 CT failure detector (CtFail)This element is instantiated in the following products: D30, D60, F60, G30, G60, L30, L60, L90, M60, N60, T35, T60.setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRef26 ORG CAP # BKR OPEN 52b setting. RsetSrcRef ObjectReference SP CAP # BKR OPEN 52b setting reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRef27 ORG CAP # REMOTE CLOSE setting. RsetSrcRef ObjectReference SP CAP # REMOTE CLOSE setting reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRef28 ORG CAP # LOCAL CLOSE setting. RsetSrcRef ObjectReference SP CAP # LOCAL CLOSE setting reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRef29 ORG CAP # AUTO CLOSE setting. RsetSrcRef ObjectReference SP CAP # AUTO CLOSE setting reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRef30 ORG CAP # BKR CLSD 52a setting. RsetSrcRef ObjectReference SP CAP # BKR CLSD 52a setting reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CBlkRef1 ORG CAP # BKR CLOSE BLK setting. RsetSrcRef ObjectReference SP CAP # BKR CLOSE BLK reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRef31 ORG CAP # CLS OVERRIDE setting. RsetSrcRef ObjectReference SP CAP # CLS OVERRIDE setting reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CLNName: ColdFXUT# LDevice inst: Ctrl UR element: Cold Load Pickup # elementdata obj. data attribute Type FC UR Name Description R/W/COp ACT COLD LOAD # OP operand Rgeneral BOOLEAN ST COLD LOAD # OP RStrVal ASG Start level of the current, which is fixed at2% of Nominal CT (0.02 pu), and it is non-configurable read only valueRsetMag AnalogueValue SP RsetMag.f FLOAT32 0.02 Runits Unit CF Runits.SIUnit ENUMERATED 1, the code for dimensionless Runits.multiplier ENUMERATED 0, the code for a multiplier of 1 RBlkRef1 ORG COLD LOAD # BLK setting RsetSrcRef ObjectReference SP COLD LOAD # BLK. reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRef1 ORG COLD LOAD # INIT setting RsetSrcRef ObjectReference SP COLD LOAD # INIT. reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CLNName: CapCtlGAPC# LDevice inst: Ctrl UR element: Capacitor control element #data obj. data attribute Type FC UR Name Description R/W/C