3-112 UR FAMILY – COMMUNICATIONS GUIDEMODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION3Table 3-132: Voltage differential stage objects3.5.2.82 Volts per Hertz (VpHz)This element is instantiated in the following products: G30, G60, L90, T60.Table 3-133: Volts per Hertz data objectsphsθ.cVal Vector MX Rphsθ.cVal.mag.f FLOAT32 Bus Vφ magnitude, withdeadbandRphsθ.units Unit CF Rphsθ.units.SIUnit ENUMERATED 1, the code for dimensionless (per unit) Rphsθ.units.multiplierENUMERATED 0, the code for a multiplier of 1 Rphsθ.db INT32U CF VDifPDIF#.BusVPh.phsθ.db R/W/Cphsθ.zeroDb INT32U CF 0 RLNName: VDif$PDIF# LDevice inst: Prot UR element: Voltage Differential element # stage $data obj. data attribute Type FC UR Name Description R/W/CStr ACD VOLT DIF # STG$ PKP operands (includingindividual three phases)Rgeneral BOOLEAN ST Logical OR of data attributesphsA, phsB and phsCRdirGeneral ENUMERATED ST 0, the code for unknown RphsA BOOLEAN ST VOLT DIF # STG$A PKP RdirPhsA ENUMERATED ST 0, the code for unknown RphsB BOOLEAN ST VOLT DIF # STG$B PKP RdirPhsB ENUMERATED ST 0, the code for unknown RphsC BOOLEAN ST VOLT DIF # STG$C PKP RdirPhsC ENUMERATED ST 0, the code for unknown ROp ACT VOLT DIF # STG$ OP operands Rgeneral BOOLEAN ST Logical OR of data attributesphsA, phsB, phsCRphsA BOOLEAN ST VOLT DIF # STG$A OP RphsB BOOLEAN ST VOLT DIF # STG$B OP RphsC BOOLEAN ST VOLT DIF # STG$C OP RBlkRefγ ORG VOLT DIF # BLK STG$ setting for settinggroup γ.RsetSrcRef ObjectReference SP VOLT DIF # BLK STG$ for groupγ.reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CLNName: VpHzPVPH# LDevice inst: Prot UR element: Volts per Hertz element #data obj. data attribute Type FC UR Name Description R/W/COp ACT VOLTS PER HERTZ # OP operand Rgeneral BOOLEAN ST VOLTS PER HERTZ # OP RDpo SPS VOLTS PER HERTZ # DPO operand RstVal BOOLEAN ST VOLTS PER HERTZ # DPO RStr ACD VOLTS PER HERTZ # PKP operand Rgeneral BOOLEAN ST VOLTS PER HERTZ # PKP operand RdirGeneral ENUMERATED ST 0 RBlkRefγ ORG VOLTS /HZ # BLOCK setting for settinggroup γRsetSrcRef ObjectReference SP VOLTS/HZ # BLOCK for group γ Reference to the data attribute to input R/CsetSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/CLNName: VDifPDIF# LDevice inst: Prot UR element: Voltage Differential element # core functionsdata obj. data attribute Type FC UR Name Description R/W/C