CHAPTER 2: MODBUS COMMUNICATION MEMORY MAPUR FAMILY – COMMUNICATIONS GUIDE 2-332Source Energy Metering (Read Only Non-Volatile) (4 or 6 Modules)B30, C60, D60,F35, F60, G30,G60, L90, M60,N60, T601D00 Source 1 Positive Watthour 0 to1000000000000Wh 0.001 F060 0" 1D02 Source 1 Negative Watthour 0 to1000000000000Wh 0.001 F060 0" 1D04 Source 1 Positive Varhour 0 to1000000000000varh 0.001 F060 0" 1D06 Source 1 Negative Varhour 0 to1000000000000varh 0.001 F060 0" 1D08 Reserved (8 items) --- --- --- F001 0" 1D10 ...Repeated for Source 2" 1D20 ...Repeated for Source 3" 1D30 ...Repeated for Source 4B30, F35, N60,T601D40 ...Repeated for Source 5" 1D50 ...Repeated for Source 6Energy Commands (Read/Write Command)B30, C60, D60,F35, F60, G30,G60, L90, M60,N60, T601D60 Energy Clear Command 0 to 1 --- 1 F126 0 (No)Source Frequency (Read Only) (2, 4, or 6 Modules)All except B90,C301D80 Frequency for Source 1 2 to 90 Hz 0.001 F003 0" 1D82 Frequency for Source 2 2 to 90 Hz 0.001 F003 0B30, C60, C70,D60, F35, F60,G30, G60, L60,L90, M60, N60,T35, T601D84 Frequency for Source 3 2 to 90 Hz 0.001 F003 0" 1D86 Frequency for Source 4 2 to 90 Hz 0.001 F003 0B30, C70, F35,N60, T35, T601D88 Frequency for Source 5 2 to 90 Hz 0.001 F003 0" 1D8A Frequency for Source 6 2 to 90 Hz 0.001 F003 0Source Demand (Read Only) (4 or 6 Modules)B30, C60, D60,F35, F60, G60,L60, L90, N60,T601E00 Source 1 Demand Ia 0 to 999999.999 A 0.001 F060 0" 1E02 Source 1 Demand Ib 0 to 999999.999 A 0.001 F060 0" 1E04 Source 1 Demand Ic 0 to 999999.999 A 0.001 F060 0" 1E06 Source 1 Demand Watt 0 to 999999.999 W 0.001 F060 0" 1E08 Source 1 Demand Var 0 to 999999.999 var 0.001 F060 0" 1E0A Source 1 Demand Va 0 to 999999.999 VA 0.001 F060 0" 1E0C Reserved (4 items) --- --- --- F001 0" 1E10 ...Repeated for Source 2" 1E20 ...Repeated for Source 3" 1E30 ...Repeated for Source 4B30, F35, N60,T601E40 ...Repeated for Source 5" 1E50 ...Repeated for Source 6Products Address Register name Range Units Step Format Default