CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)UR FAMILY – COMMUNICATIONS GUIDE 3-333LNName: LPHD1LDevice inst: MasterUR element:data obj. data attribute Type FC UR Name Description R/W/CoperT imeout INT32U CF 0 RSim SPC Will accept simulated GOOSE messages RstVal BOOLEAN ST RctlModel CtlModels CF 0 R/CMMSConnectsMV Number of MMS client connections active Rmag AnalogueValue MX Rmag.i INT32 5 minus the value of “MMS TCP(max 5)” Runits Unit CF Runits.SIUnit ENUMERATED 1, the code for dimensionless Runits.multiplier ENUMERATED 0, the code for a multiplier of 1 RsVC ScaledValueConf igCF RsVC.scaleFactor FLOAT32 1 RsVC.offset FLOAT32 0 RAnyErr SPS ANY SELF TESTS operand RstVal BOOLEAN ST ANY SELF TESTS RMajorErr SPS ANY MAJOR ERROR operand RstVal BOOLEAN ST ANY MAJOR ERROR RMinorErr SPS ANY MINOR ERROR operand RstVal BOOLEAN ST ANY MINOR ERROR RBatFail SPS BATTERY FAIL operand RstVal BOOLEAN ST BATTERY FAIL RClkUnsynchSPS CLOCK UNSYNCHRONIZED operand RstVal BOOLEAN ST CLOCK UNSYNCHRONIZED RRlyUTCTms SPS relay UTC time in seconds RstVal BOOLEAN ST Modbus register 41A0h value,i.e., “Relay time clock set time”register value after converting toUTCRDrcDevOff SPS DIRECT DEVICE OFF operand RstVal BOOLEAN ST DIRECT DEVICE OFF RDrcRingBrk SPS DIRECT RING BREAK operand RstVal BOOLEAN ST DIRECT RING BREAK REqpMismat SPS EQUIPMENT MISMATCH operand RstVal BOOLEAN ST EQUIPMENT MISMATCH RFlexErrTkn SPS FLEXLOGIC ERR TOKEN operand RstVal BOOLEAN ST FLEXLOGIC ERR TOKEN RIrigbFail SPS IRIG-B FAILURE operand RstVal BOOLEAN ST IRIG-B FAILURE RLatchErr SPS LATCHING OUT ERROR operand RstVal BOOLEAN ST LATCHING OUT ERROR ROscilGOOSESPS Oscillatory GOOSE operand RstVal BOOLEAN ST Oscillatory GOOSE RFrstEthFail SPS FIRST ETHERNET FAIL operand RstVal BOOLEAN ST FIRST ETHERNET FAIL RPtpFail SPS PTP FAILURE operand RstVal BOOLEAN ST PTP FAILURE R