3-218 UR FAMILY – COMMUNICATIONS GUIDEMODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION3Trouble SPS Trouble operand or LED.The LED TROUBLE operand.The SH STAT GND TRB OP operand.SubHaPHIZ, LEDsIHMITx1 SPS Transmit signal.The DCUB TX1 operand.The DUTT TX1 operand.The HYBRID POTT TX1 operand.The POTT1 TX1 operand.The PUTT TX1 operand.DCUB_PSCH, DUTT_PSCH,HPOTT_PSCH, POTT_PSCH,POTT1_PSCH, PUTT_PSCHTxStop1 SPS Transmit signal stop.The DIR BLOCK1 TX1 STOP operand.DCB_PSCH, DCB1_PSCHUnA1 SPS Undercurrent pickup.This operand operates when an open pole condition is detected due toundercurrent in phase A, B, or C.The OPEN POLE I< phase A/B/C operand.LinPkpPIOC, OpnPlΘSCBRUNotPrgm SPS The Product Setup > Installation > Relay Settings setting is not programmed.The UNIT NOT PROGRAMMED operand.LPHDUnV SPS Undervoltage pickup.The LINE PICKUP UV PKP operand.LinPkpPIOCUpdateTms ING Periodic update time Master/LLN0UsrPrgmLED1 SPS LED indication - User Programmable LED status. For enhanced and standard frontpanels.The LED USER 1 operand.LEDsIHMIV1Src CMV V1 Voltage phasor.SYNCHROCHECK 1 V1 voltage phasor, in primary volts.SynChkRSYNV2Src CMV V2 Voltage phasor.SYNCHROCHECK 1 V2 voltage phasor, in primary volts.SynChkRSYNVabRMS MV Phase AB Voltage RMS. SRC 1 Phase AB Voltage RMS, in primary Volts. ACsrcMMXUVADmd MV Apparent power demand in VA.SRC 1 DMD VA, in primary volt ampere.DmdMtrMMTRVAMaxDmdDt MV Max apparent power demand in VA with associated date/time stamp. The ClcMthcannot be used for MAX, as the time stamp definition of IEC 61850 is differentfrom UR.SRC 1 DMD VA, in primary volt ampere, with associated date, SRC 1 DMD VA DATE.DmdMtrMMTRVArDmd MV Reactive power demand in VAR.SRC 1 DMD VAR, in primary volt ampere reactive.DmdMtrMMTRVArMaxDmdDt MV Max reactive power demand in VAR with associated date/time stamp. The ClcMthcannot be used for MAX, as the time stamp definition of IEC 61850 is differentfrom UR.SRC 1 DMD VAR, in primary volt ampere reactive, with associated date, SRC 1DMD VAR DATE.DmdMtrMMTRVaRMS MV Phase A Voltage RMS.SRC 1 Phase AG Voltage RMS, in primary volts.ACsrcMMXUVaux CMV Auxiliary voltage (fourth input in a voltage AC bank).SRC 1 Auxiliary Voltage phasor, in primary volts.ACsrcMMXNVauxRMS MV Auxiliary voltage RMS (fourth input in a voltage AC bank).SRC 1 Auxiliary Voltage RMS, in primary volts.ACsrcMMXNVbcRMS MV Phase BC Voltage RMS.SRC 1 Phase BC Voltage RMS, in primary Volts.ACsrcMMXUVbRMS MV Phase B Voltage RMS.SRC 1 Phase BG Voltage RMS, in primary volts.ACsrcMMXUVcaRMS MV Phase CA Voltage RMS.SRC 1 Phase CA Voltage RMS, in primary Volts.ACsrcMMXUVcRMS MV Phase A Voltage RMS.SRC 1 Phase CG Voltage RMS, in primary volts.ACsrcMMXUVolLoc CMV Composite Voltage at the Local Terminal. Local Vcomp phasor, in primary volts. VCompMMXUData objectnameCDC Semantics Used in logical nodes…