2-146 UR FAMILY – COMMUNICATIONS GUIDEMEMORY MAP CHAPTER 2: MODBUS COMMUNICATION2Cold Load Pickup (Read/Write Setting) (2 or 6 Modules)F35, F60 9F30 Cold Load Pickup 1 Function 0 to 1 --- 1 F102 0 (Disabled)" 9F31 Cold Load Pickup 1 Initiate 0 to 4294967295 --- 1 F300 0" 9F33 Cold Load Pickup 1 Block 0 to 4294967295 --- 1 F300 0" 9F35 Outage Time Before Cold Load Pickup 1 0 to 1000 s 1 F001 1000" 9F36 On Load Time Before Reset 1 0 to 1000000 s 0.001 F003 100000" 9F38 Cold Load Pickup 1 Source 0 to 5 --- 1 F167 0 (SRC 1)" 9F39 Cold Load Pickup 1 Reserved 0 to 65535 --- 1 F001 0" 9F3A ...Repeated for Cold Load Pickup 2F35 9F44 ...Repeated for Cold Load Pickup 3" 9F4E ...Repeated for Cold Load Pickup 4" 9F58 ...Repeated for Cold Load Pickup 5" 9F62 ...Repeated for Cold Load Pickup 6B90 Direct Outputs (Read/Write Setting) (256 Modules)B90 A000 Direct Output 1 Operand 0 to 4294967295 --- 1 F300 0" A002 Direct Output 1 Events 0 to 1 --- 1 F102 0 (Disabled)" A003 ...Repeated for Direct Output 2" A006 ...Repeated for Direct Output 3" A009 ...Repeated for Direct Output 4" A00C ...Repeated for Direct Output 5" A00F ...Repeated for Direct Output 6" A012 ...Repeated for Direct Output 7" A015 ...Repeated for Direct Output 8" A018 ...Repeated for Direct Output 9" A01B ...Repeated for Direct Output 10... ..." A093 ...Repeated for Direct Output 50" A129 ...Repeated for Direct Output 100... ..." A1BF ...Repeated for Direct Output 150... ..." A255 ...Repeated for Direct Output 200... ..." A2FD ...Repeated for Direct Output 256Broken Rotor Bar Detection (Read Only Actual Values)M60 A020 Broken Rotor Bar Component Level –100 to 0 dB 0.1 F002 –1000" A021 Broken Rotor Bar Component Frequency 0 to 76 Hz 0.01 F001 0" A022 Motor Load at Broken Rotor Bar Calculation 0 to 1.5 × FLA 0.01 F001 0" A023 Motor Load Deviation at Broken Rotor BarCalculation0 to 1.5 × FLA 0.01 F001 0" A024 Time Stamp at Broken Rotor BarCalculation0 to 4294967295 --- 1 F050 0" A026 Maximum Broken Rotor Bar ComponentLevel–100 to 0 dB 0.1 F002 –1000" A027 Maximum Broken Rotor Bar ComponentFrequency0 to 76 Hz 0.01 F001 0" A028 Motor Load at Broken Rotor Bar Maximum 0 to 1.5 × FLA 0.01 F001 0Products Address Register name Range Units Step Format Default