CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)UR FAMILY – COMMUNICATIONS GUIDE 3-3933.5.2.5 B90 breaker failure (B_BFai)This element is instantiated in the following products: B90.Table 3-23: B90 breaker failure current data objectsTable 3-24: B90 breaker failure logic data objectsOp ACT AUX UV# OP operand Rgeneral BOOLEAN ST AUX UV# OP RDpo SPS AUX UV# DPO operand, which is theinverse of AUX UV PKPRstVal BOOLEAN ST AUX UV# DPO RBlkRefγ ORG AUX UV# BLOCK setting for setting groupγ.RsetSrcRef ObjectReference SP AUX UV# BLOCK for group γ. reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CLNName: B_BFaiPIOC# LDevice inst: Prot UR element: B90 BREAKER FAILURE CURRENT SUPV # functiondata obj. data attribute Type FC UR Name Description R/W/COp ACT BKRSUPV # SUPV OP operand Rgeneral BOOLEAN ST BKRSUPV # SUPV OP ROpHiSet ACT BKRSUPV # HISET OP operand Rgeneral BOOLEAN ST BKRSUPV # HISET OP ROpLoSet ACT BKRSUPV # LOSET OP operand Rgeneral BOOLEAN ST BKRSUPV # LOSET OP RLNName: B_BFaiRBRF# LDevice inst: Prot UR element: B90 BREAKER FAILURE logic elementdata obj. data attribute Type FC UR Name Description R/W/COpEx ACT BKRFAIL # TRIP OP operand Rgeneral BOOLEAN ST BKRFAIL # TRIP OP ROpIn ACT BKRFAIL # RETRIP operand Rgeneral BOOLEAN ST re-trip operand BKRFAIL #RETRIPRBkrOp& SPS BKRFAIL # T& OP operand RstVal BOOLEAN ST BKRFAIL # T& OP RInRefγ01 ORG BF# INITIATE setting for setting group γ. RsetSrcRef ObjectReference SP BF# INITIATE for group γ. reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRefγ02 ORG BF# AMP SUPV OP A setting for settinggroup γ.RsetSrcRef ObjectReference SP BF# AMP SUPV OP A for group γ.reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRefγ03 ORG BF# AMP SUPV OP B setting for settinggroup γ.RsetSrcRef ObjectReference SP BF# AMP SUPV OP B for group γ.reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRefγ04 ORG BF# AMP SUPV OP C setting for settinggroup γ.RsetSrcRef ObjectReference SP BF# AMP SUPV OP C for group γ.reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRefγ05 ORG BF# BKR POS1 setting for setting group γ. RsetSrcRef ObjectReference SP BF# BKR POS1 for group γ. reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRefγ06 ORG BF# BKR POS2 setting for setting group γ. RsetSrcRef ObjectReference SP BF# BKR POS2 for group γ. reference to the data attribute to input R/CLNName: AuxUvPTUV# LDevice inst: Prot UR element: Auxiliary Undervoltage element# functionsdata obj. data attribute Type FC UR Name Description R/W/C