CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)UR FAMILY – COMMUNICATIONS GUIDE 3-8133.5.2.51 Permissive overreaching transfer trip 1 (POTT1_)This element is instantiated in the following products: D60, L90.Table 3-84: POTT1 data objectsInRef5 ORG POTT ECHO COND setting RsetSrcRef ObjectReference SP POTT ECHO COND Reference to the data attribute to input R/CsetSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/CInRef6 ORG GND DIR O/C FWD setting RsetSrcRef ObjectReference SP GND DIR O/C FWD Reference to the data attribute to input R/CsetSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/CInRef1 ORG POTT RX1 setting RsetSrcRef ObjectReference SP POTT RX1 Reference to the data attribute to input R/CsetSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/CInRef2 ORG POTT RX2 setting RsetSrcRef ObjectReference SP POTT RX2 Reference to the data attribute to input R/CsetSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/CInRef3 ORG POTT RX3 setting RsetSrcRef ObjectReference SP POTT RX3 Reference to the data attribute to input R/CsetSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/CInRef4 ORG POTT RX4 setting RsetSrcRef ObjectReference SP POTT RX4 Reference to the data attribute to input R/CsetSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/CLNName: POTT1_PSCH1 LDevice inst: Prot UR element: Permissive Over-reaching Transfer Trip 1 elementdata obj. data attribute Type FC UR Name Description R/W/COp ACT POTT1 OP operand Rgeneral BOOLEAN ST POTT1 OP RphsA BOOLEAN ST POTT1 TRIP A RphsB BOOLEAN ST POTT1 TRIP B RphsC BOOLEAN ST POTT1 TRIP C RTr3p ACT Instantiated only on products with singlepole tripping.Rgeneral BOOLEAN ST POTT1 TRIP 3P RTx1 SPS POTT1 TX1 operand RstVal BOOLEAN ST POTT1 TX1 RTx2 SPS Instantiated only on products with singlepole tripping.RstVal BOOLEAN ST POTT1 TX2 RTx3 SPS Instantiated only on products with singlepole tripping.RstVal BOOLEAN ST POTT1 TX3 RTx4 SPS Instantiated only on products with singlepole tripping.RstVal BOOLEAN ST POTT1 TX4 RBlkRef1 ORG POTT1 SCHEME BLOCK setting. RsetSrcRef ObjectReference SP POTT1 SCHEME BLOCK. reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRef5 ORG POTT1 ECHO COND setting. RsetSrcRef ObjectReference SP POTT1 ECHO COND reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRef6 ORG DIR FWD1 setting. RsetSrcRef ObjectReference SP DIR FWD1 reference to the data attribute to input R/CLNName: POTT_PSCH1 LDevice inst: Prot UR element: Permissive Over-reaching Transfer Trip elementdata obj. data attribute Type FC UR Name Description R/W/C