GE Multilin N60 Network Stability and Synchrophasor Measurement System 4-274 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE42. Press the MESSAGE RIGHT key until the ACCESS LEVEL message appears on the display.3. Press the MESSAGE DOWN key until the CHANGE LOCAL PASSWORDS message appears on the display.4. Press the MESSAGE RIGHT key until the CHANGE SETTING PASSWORD or CHANGE COMMAND PASSWORD messageappears on the display.5. After the CHANGE...PASSWORD message appears on the display, press the VALUE UP or DOWN key to change theselection to “Yes”.6. Press the ENTER key and the display will prompt you to ENTER NEW PASSWORD.7. Type in a numerical password (up to 10 characters) and press the ENTER key.8. When the VERIFY NEW PASSWORD is displayed, re-type in the same password and press ENTER.9. When the NEW PASSWORD HAS BEEN STORED message appears, your new Setting (or Command) Password will beactive.f) CHANGING EXISTING PASSWORDTo change an existing password, follow the instructions in the previous section with the following exception. A message willprompt you to type in the existing password (for each security level) before a new password can be entered.In the event that a password has been lost (forgotten), submit the corresponding encrypted password from the PASSWORDSECURITY menu to the Factory for decoding.g) INVALID PASSWORD ENTRYBy default, when an incorrect Command or Setting password has been entered via the faceplate interface three timeswithin three minutes, the LOCAL ACCESS DENIED FlexLogic™ operand is set to “On” and the N60 does not allow settings orcommand level access via the faceplate interface for the next five minutes.By default, when an incorrect Command or Setting password has been entered via any external communications interfacethree times within three minutes, the REMOTE ACCESS DENIED FlexLogic™ operand is set to “On” and the N60 does notallow settings or command access via the any external communications interface for five minutes. The REMOTE ACCESSDENIED FlexLogic™ operand is set to “Off” after five minutes for a Command password or 30 minutes for a Settings pass-word.These default settings can be changed in EnerVista under Settings > Product Setup > Security. SECURITYACCESS LEVEL:Restricted CHANGE LOCAL PASSWORDSCHANGE COMMANDPASSWORD: NoCHANGE SETTINGPASSWORD: NoENCRYPTED COMMANDPASSWORD: ---------ENCRYPTED SETTINGPASSWORD: ---------CHANGE SETTINGPASSWORD: NoCHANGE SETTINGPASSWORD: YesENTER NEWPASSWORD: ##########VERIFY NEWPASSWORD: ##########NEW PASSWORDHAS BEEN STORED