5-94 N60 Network Stability and Synchrophasor Measurement System GE Multilin5.4 SYSTEM SETUP 5 SETTINGS5l) PMU RECORDINGPATH: SETTINGS SYSTEM SETUP PHASOR... PHASOR MEASUREMENT UNIT 1 PMU 1 RECORDINGEach logical phasor measurement unit (PMU) is associated with a recorder. The triggering condition is programmed via thePMU 1 TRIGGERING menu. The recorder works with polar values using resolution as in the PMU actual values. PMU 1 RECORDINGPMU 1 RECORDINGRATE: 10/secRange: 1, 2, 4, 5, 10, 12, 15, 20, 25, 30, 50, or 60 timesper secondMESSAGE PMU 1 NO OF TIMEDRECORDS: 10Range: 2 to 128 in steps of 1MESSAGE PMU 1 TRIGGER MODE:Automatic OverwriteRange: Automatic Overwrite, ProtectedMESSAGE PMU 1 TIMED TRIGGERPOSITION: 10%Range: 1 to 50% in steps of 1MESSAGE PMU 1 REC PHS-1:PMU 1 V1Range: available synchrophasor valuesMESSAGE PMU 1 REC PHS-1NM: GE-UR-PMU-V1Range: 16 character ASCII string↓MESSAGE PMU 1 REC PHS-14:OffRange: available synchrophasor valuesMESSAGE PMU 1 REC PHS-14NM: GE-UR-PMU-PHS-14Range: 16 character ASCII stringMESSAGE PMU 1 REC A-CH-1:OffRange: available FlexAnalog valuesMESSAGE PMU 1 REC A-CH-1NM: AnalogChannel1Range: 16 character ASCII string↓MESSAGE PMU 1 REC A-CH-16:OffRange: available FlexAnalog valuesMESSAGE PMU 1 REC A-CH-16NM: AnalogChannel16Range: 16 character ASCII stringMESSAGE PMU 1 REC D-CH-1:OffRange: FlexLogic™ operandMESSAGE PMU 1 REC D-CH-1NM: DigitalChannel1Range: 16 character ASCII string↓MESSAGE PMU 1 REC D-CH-16:OffRange: FlexLogic™ operandMESSAGE PMU 1 REC D-CH-16NM: DigitalChannel16Range: 16 character ASCII string