5-200 N60 Network Stability and Synchrophasor Measurement System GE Multilin5.8 INPUTS AND OUTPUTS 5 SETTINGS5The GOOSE analog input FlexAnalog™ values are available for use in other N60 functions that use FlexAnalog™ values.5.8.15 IEC 61850 GOOSE INTEGERSPATH: SETTINGS INPUTS/OUTPUTS IEC 61850 GOOSE UINTEGERS GOOSE UINTEGER INPUT 1(16)The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger™ values between any two UR-series devices. The following settings are available for each GOOSE uinteger input.• UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device isoffline and the UINTEGER 1 DEFAULT MODE is set to “Default Value”.This setting is stored as a 32-bit unsigned integernumber.• UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of theGOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is“Default Value”, then the value of the GOOSE uinteger input is defined by the UINTEGER 1 DEFAULT setting.The GOOSE integer input FlexInteger™ values are available for use in other N60 functions that use FlexInteger™ values.SOURCE ENERGY(Positive and Negative Watthours,Positive and Negative Varhours)EBASE = 10000 MWh or MVAh, respectivelySOURCE POWER PBASE = maximum value of V BASE × IBASE for the +IN and –IN inputsSOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputsSYNCHROCHECK(Max Delta Volts)VBASE = maximum primary RMS value of all the sources related to the +IN and –IN inputs GOOSE UINTEGER INPUT 1UINTEGER 1 DEFAULT:1000Range: 0 to 429496295 in steps of 1MESSAGE UINTEGER 1 DEFAULTMODE: Default ValueRange: Default Value, Last KnownTable 5–14: GOOSE ANALOG INPUT BASE UNITS (Sheet 2 of 2)ELEMENT BASE UNITS