GE Multilin N60 Network Stability and Synchrophasor Measurement System 5-415 SETTINGS 5.2 PRODUCT SETUP5When changes are made to the oscillography settings, all existing oscillography records will be CLEARED.b) DIGITAL CHANNELSPATH: SETTINGS PRODUCT SETUP OSCILLOGRAPHY DIGITAL CHANNELSA DIGITAL 1(63) CHANNEL setting selects the FlexLogic™ operand state recorded in an oscillography trace. The length ofeach oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored.Upon startup, the relay will automatically prepare the parameter list.c) ANALOG CHANNELSPATH: SETTINGS PRODUCT SETUP OSCILLOGRAPHY ANALOG CHANNELSThese settings select the metering actual value recorded in an oscillography trace. The length of each oscillography tracedepends in part on the number of parameters selected here. Parameters set to “Off” are ignored. The parameters availablein a given relay are dependent on:• The type of relay,• The type and number of CT/VT hardware modules installed, and• The type and number of analog input hardware modules installed.Upon startup, the relay will automatically prepare the parameter list. A list of all possible analog metering actual valueparameters is presented in Appendix A: FlexAnalog parameters. The parameter index number shown in any of the tables isused to expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the listof parameters via the relay keypad and display - entering this number via the relay keypad will cause the correspondingparameter to be displayed.All eight CT/VT module channels are stored in the oscillography file. The CT/VT module channels are named as follows:<slot_letter><terminal_number>—<I or V><phase A, B, or C, or 4th input>The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IB desig-nates the IB signal on terminal 2 of the CT/VT module in slot F.If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces willappear. DIGITAL CHANNELSDIGITAL CHANNEL 1:OffRange: FlexLogic™ operandMESSAGE DIGITAL CHANNEL 2:OffRange: FlexLogic™ operandMESSAGE DIGITAL CHANNEL 3:OffRange: FlexLogic™ operand↓MESSAGE DIGITAL CHANNEL 63:OffRange: FlexLogic™ operand ANALOG CHANNELSANALOG CHANNEL 1:OffRange: Off, any FlexAnalog parameterSee Appendix A for complete list.MESSAGE ANALOG CHANNEL 2:OffRange: Off, any FlexAnalog parameterSee Appendix A for complete list.MESSAGE ANALOG CHANNEL 3:OffRange: Off, any FlexAnalog parameterSee Appendix A for complete list.↓MESSAGE ANALOG CHANNEL 16:OffRange: Off, any FlexAnalog parameterSee Appendix A for complete list.NOTE