GE Multilin N60 Network Stability and Synchrophasor Measurement System 5-1235 SETTINGS 5.6 GROUPED ELEMENTS55.6.3 POWER SWING DETECTPATH: SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) POWER SWING DETECT POWER SWING DETECTPOWER SWINGFUNCTION: DisabledRange: Disabled, EnabledMESSAGE POWER SWINGSOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6MESSAGE POWER SWINGSHAPE: Mho ShapeRange: Mho Shape, Quad ShapeMESSAGE POWER SWINGMODE: Two StepRange: Two Step, Three StepMESSAGE POWER SWINGSUPV: 0.600 puRange: 0.050 to 30.000 pu in steps of 0.001MESSAGE POWER SWING FWDREACH: 50.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01MESSAGE POWER SWING QUAD FWDREACH MID: 60.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01MESSAGE POWER SWING QUAD FWDREACH OUT: 70.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01MESSAGE POWER SWING FWDRCA: 75°Range: 40 to 90° in steps of 1MESSAGE POWER SWING REVREACH: 50.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01MESSAGE POWER SWING QUAD REVREACH MID: 60.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01MESSAGE POWER SWING QUAD REVREACH OUT: 70.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01MESSAGE POWER SWING REVRCA: 75°Range: 40 to 90° in steps of 1MESSAGE POWER SWING OUTERLIMIT ANGLE: 120°Range: 40 to 140° in steps of 1MESSAGE POWER SWING MIDDLELIMIT ANGLE: 90°Range: 40 to 140° in steps of 1MESSAGE POWER SWING INNERLIMIT ANGLE: 60°Range: 40 to 140° in steps of 1MESSAGE POWER SWING OUTERRGT BLD: 100.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01MESSAGE POWER SWING OUTERLFT BLD: 100.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01MESSAGE POWER SWING MIDDLERGT BLD: 100.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01MESSAGE POWER SWING MIDDLELFT BLD: 100.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01MESSAGE POWER SWING INNERRGT BLD: 100.00 ΩRange: 0.10 to 500.00 ohms in steps of 0.01