1-10 N60 Network Stability and Synchrophasor Measurement System GE Multilin1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED1 7. Enter the desired name in the “Device Name” field and a description (optional) of the site.8. Select “Ethernet” from the Interface drop-down list. This will display a number of interface parameters that must beentered for proper Ethernet functionality.Figure 1–5: CONFIGURING ETHERNET COMMUNICATIONS9. Enter the relay IP address specified in the front panel SETTINGS PRODUCT SETUP COMMUNICATIONS NET-WORK IP ADDRESS) in the “IP Address” field.10. Enter the relay slave address and Modbus port address values from the respective settings in the front panel SETTINGS PRODUCT SETUP COMMUNICATIONS MODBUS PROTOCOL menu.11. Click the Read Order Code button to connect to the N60 device and upload the order code. If an communicationserror occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relaysetting values.12. Click OK when the relay order code has been received. The new device will be added to the Site List window (orOnline window) located in the top left corner of the main EnerVista UR Setup window.The Site Device has now been configured for Ethernet communications. Proceed to the Connecting to the N60 section tobegin communications.1.3.4 USING THE QUICK CONNECT FEATUREa) USING QUICK CONNECT VIA THE FRONT PANEL RS232 PORTBefore starting, verify that the serial cable is properly connected from the laptop computer to the front panel RS232 portwith a straight-through 9-pin to 9-pin RS232 cable.1. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD oronline from http://www.gedigitalenergy.com/multilin). See the Software Installation section for installation details.2. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.