GE Multilin N60 Network Stability and Synchrophasor Measurement System 5-1195 SETTINGS 5.5 FLEXLOGIC™55.5.9 FLEXMATHa) SUMMATORPATH: SETTINGS FLEXLOGIC FLEXMATH SUMMATOR SUMMATOR 1(6)Six identical summators are available in each N60 device.Each summator has six inputs and a scaling factor is provided for each input. The scaling factors can be set to +1 and –1allowing straight addition and subtraction of the inputs. A FlexLogic™ operand provided for each input can dynamicallyinclude/exclude the input from calculations. SUMMATOR 1SUMMATOR 1 FUNCTION:DisabledRange: Disabled, EnabledMESSAGE SUMMATOR 1 INPUTMODE: SignedRange: Signed, AbsoluteMESSAGE SUMMATOR 1 HOLD:OffRange: FlexLogic™ operandMESSAGE SUMMATOR 1 PICKUP:1000.000Range: –2000000.000 to 2000000.000 in steps of 0.001MESSAGE SUMMATOR 1HYSTERESIS: 3.0%Range: 0.1 to 50.0% in steps of 0.1MESSAGE SUMMATOR 1 UNITS: Range: 4 alphanumeric charactersMESSAGE SUMMATOR 1 PU BASE:1Range: 1 to 2000000 in steps of 1MESSAGE SUMMATOR 1 INPUT1:OffRange: Off, any FlexAnalog parameter.See Appendix A for complete list.MESSAGE SUMMATOR 1 INPUT2:OffRange: Off, any FlexAnalog parameter.See Appendix A for complete list.↓MESSAGE SUMMATOR 1 INPUT6:OffRange: Off, any FlexAnalog parameter.See Appendix A for complete list.MESSAGE SUMMATOR 1 SCALE1:1.000000Range: –2000.000000 to 2000.000000 in steps of0.000001MESSAGE SUMMATOR 1 SCALE2:1.000000Range: –2000.000000 to 2000.000000 in steps of0.000001↓MESSAGE SUMMATOR 1 SCALE6:1.000000Range: –2000.000000 to 2000.000000 in steps of0.000001MESSAGE SUMMATOR 1 POS1:OffRange: FlexLogic™ operandMESSAGE SUMMATOR 1 POS2:OffRange: FlexLogic™ operand↓MESSAGE SUMMATOR 1 POS6:OffRange: FlexLogic™ operandMESSAGE SUMMATOR 1 EVENTS:DisabledRange: Disabled, Enabled