5-28 N60 Network Stability and Synchrophasor Measurement System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5– Set REMOTE DEVICE 1 ETYPE APPID to match the ETHERTYPE application ID from the transmitting device. This is“0” in the example above.– Set the REMOTE DEVICE 1 DATASET value. This value represents the dataset number in use. Since we are usingconfigurable GOOSE 1 in this example, program this value as “GOOSEIn 1”.3. Configure the Boolean data by making the following changes in the INPUTS/OUTPUTS REMOTE INPUTS REMOTEINPUT 1 settings menu:– Set REMOTE IN 1 DEVICE to “GOOSEOut_1”.– Set REMOTE IN 1 ITEM to “Dataset Item 2”. This assigns the value of the GGIO3.ST.Ind1.stVal single point statusitem to remote input 1.4. Configure the analog data by making the following changes in the INPUTS/OUTPUTS IEC 61850 GOOSE ANALOGINPUTS settings menu:– Set the IEC61850 GOOSE ANALOG INPUT 1 DEFAULT VALUE to “60.000”.– Enter “Hz” for the IEC61850 GOOSE ANALOG INPUT 1 UNITS setting.The GOOSE analog input 1 can now be used as a FlexAnalog™ value in a FlexElement™ or in other settings. The N60must be rebooted (control power removed and re-applied) before these settings take effect.The value of GOOSE analog input 1 in the receiving device will be determined by the MMXU1.MX.Hz.mag.f value in thesending device. This MMXU value is determined by the source 1 frequency value and the MMXU Hz deadband setting ofthe sending device.Remote input 1 can now be used in FlexLogic™ equations or other settings. The N60 must be rebooted (control powerremoved and re-applied) before these settings take effect.The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal valuein the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-plete SCD file is created by third party substation configurator software.For intercommunication between N60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-tains the same DNA and UserSt bit pairs that are included in GSSE messages. All GOOSE messages transmitted by theN60 (DNA/UserSt dataset and configurable datasets) use the IEC 61850 GOOSE messaging services (for example, VLANsupport).Set the CONFIG GSE 1 FUNCTION function to “Disabled” when configuration changes are required. Once changes areentered, return the CONFIG GSE 1 FUNCTION to “Enabled” and restart the unit for changes to take effect.PATH: SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE CONFIGURATION TRANSMISSION CONFIGURABLE GOOSE CONFIGURABLE GOOSE 1(8) CONFIG GSE 1(64) DATA ITEMSTo create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status indication and its associated qual-ity flags, the following dataset items can be selected: “GGIO1.ST.Ind1.stVal” and “GGIO1.ST.Ind1.q”. The N60 will then cre-ate a dataset containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic™operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con-taining the defined dataset. CONFIG GSE 1 DATASET ITEMSITEM 1:GGIO1.ST.Ind1.stValRange: all valid MMS data item references fortransmitted dataMESSAGE ITEM 2:GGIO1.ST.IndPos1.stVRange: all valid MMS data item references fortransmitted dataMESSAGE ITEM 3:NoneRange: all valid MMS data item references fortransmitted data↓MESSAGE ITEM 64:NoneRange: all valid MMS data item references fortransmitted dataNOTE