6-26 N60 Network Stability and Synchrophasor Measurement System GE Multilin6.4 RECORDS 6 ACTUAL VALUES66.4.5 BREAKER MAINTENANCEPATH: ACTUAL VALUES RECORDS MAINTENANCE BREAKER 1There is an identical menu for each of the breakers. The BKR 1 ARCING AMP values are in units of kA 2 -cycles. Refer to theCOMMANDS CLEAR RECORDS menu for clearing breaker arcing current records. The BREAKER OPERATING TIME isdefined as the slowest operating time of breaker poles that were initiated to open. BREAKER 1BKR 1 ARCING AMP φA:0.00 kA2-cycMESSAGE BKR 1 ARCING AMP φB:0.00 kA2-cycMESSAGE BKR 1 ARCING AMP φC:0.00 kA2-cycMESSAGE BKR 1 OPERATING TIMEφA: 0 msMESSAGE BKR 1 OPERATING TIMEφB: 0 msMESSAGE BKR 1 OPERATING TIMEφC: 0 msMESSAGE BKR 1 OPERATINGTIME: 0 ms