14 • Vacon apfiff09 marineTel. +35855.1 Monitoring valuesThe monitoring values are the actual values of parameters and signals as well as statusesand measurements.Note for DriveSynch Systems:In a DriveSynch system, only Master drive monitoring signals are reliable.Only directly measured values are reliable in follower units. Even the Output Frequency ofDriveSynch follower is not directly observed and thus may not show actual output frequencythat is controlled by DriveSynch Master Drive.Code Parameter Unit Form. ID DescriptionV1.1 Output frequency Hz #,## 1 Output frequency to motorV1.2 Frequency reference Hz #,## 25 Frequency reference to motor controlV1.3 Motor speed rpm # 2 Motor speed in rpmV1.4 Motor current A Varies 3 1 s linear filteringV1.5 Motor torque % #,# 4 In % of Motor nominal torqueV1.6 Motor Power % #,# 5V1.7 Motor voltage V #,# 6 Calculated motor voltageV1.8 DC link voltage V # 7 Measured DC voltage, filtered.V1.9 Unit temperature C # 8 Heatsink temperatureV1.10 Motor temperature % # 9 Calculated motor temperature, trip 105 %V1.11 Analogue input 1 % #,## 13 AI1, unfiltered.V1.12 Analogue input 2 % #,## 14 AI2, unfiltered.V1.13 Analogue input 3 % #,## 27 AI3, unfiltered.V1.14 Analogue input 4 % #,## 28 AI4, unfiltered.V1.15 Analogue Out 1 % #,## 26 AO1V1.16 Analogue Out 2 % #,## 31 AO2V1.17 Analogue Out 3 % #,## 32 AO3V1.18 Analogue Out 4 % #,## 1526V1.19 DIN1, DIN2, DIN3 15 Digital input statusesV1.20 DIN4, DIN5, DIN6 16 Digital input statusesV1.21 Power Reference % #,# 1700 Used power referenceV1.22 PT-100 Temperature Cº #,# 42 Highest temperature of OPTB8 board. 4 sfiltering.G1.23 Multimonitoring items Displays three selectable monitoringvaluesTable 5-1. Monitoring values