apfiff09 marine vacon • 6524-hour support +358 (056.12.4 Speed error monitoringCode Parameter Min Max Unit Default Cust ID NoteP2.12.4.1 Speed Error Mode 0 3 0 7520=No response1=Warning2=Fault,stop acc. to 2.3.23=Fault,stop by coastingP2.12.4.2 Speed Error Limit 0,0 100,0 % 5,0 753P2.12.4.3 Speed Fault Delay 0,00 100,00 S 0,1 754Table 6-29. Speed error monitoring6.12.5 Motor thermal protectionsCode Parameter Min Max Unit Default Cust ID NoteP2.12.5.1Thermalprotection of themotor0 3 2 7040=No response1=Warning2=Fault,stop acc. to 2.3.23=Fault,stop by coastingP2.12.5.2Motor ambienttemperaturefactor 100,0 100,0 % 0,0 705P2.12.5.3 Motor coolingfactor at zero speed 0,0 150,0 % 40,0 706P2.12.5.4 Motor thermal timeconstant 1 200 min 45 707P2.12.5.5 Motor duty cycle 0 100 % 100 708P2.12.5.6 Response tothermistor fault 0 3 2 732 See P2.12.5.1P2.12.5.7 Over LoadResponse 0 2 1 18380=No response1=Warning2=FaultP2.12.5.8 Over Load Signal 0 2 0 18370=Not Used1=Current2=Torque3=PowerP2.12.5.9 Over LoadMaximum Input 0,0 300,0 % 150,0 1839P2.12.5.10 Over Loadmaximum Step 0 10000 200 1840P2.12.5.11 Over Current TripLimit 0 1000,0 % 0 1904Software over current limitof motor nominal current,0 = disabledTable 6-30. Motor thermal protections6.12.6 Living Zero monitoringCode Parameter Min Max Unit Default Cust ID NoteP2.12.6.1 Response to 4mAreference fault 0 5 0 7000=No response1=Warning2=Warning+Previous Freq.3=Wrng+PresetFreq 2.12.6.24=Fault,stop acc. to 2.3.25=Fault,stop by coastingP2.12.6.2 4mA reference faultfrequency 0,00 P2.1.2 Hz 0,00 728Table 6-31. Living zero monitoring