66 • Vacon apfiff09 marineTel. +35856.12.7 Underload protectionCode Parameter Min Max Unit Default Cust ID NoteP2.12.7.1 Underload protection 0 3 0 7130=No response1=Warning2=Fault,stop acc. to 2.3.23=Fault,stop by coastingP2.12.7.2 Field weakening areaload 10,0 150,0 % 50,0 714P2.12.7.3 Zero frequency load 5,0 150,0 % 10,0 715P2.12.7.4 Underloadprotection time limit 2,00 600,00 s 20,00 716Table 6-32. Underload protection6.12.8 Earth Fault protectionCode Parameter Min Max Unit Default Cust ID NoteP2.12.8.1 Earth fault protection 0 3 2 7030=No response1=Warning2=Fault,stop acc. to 2.3.23=Fault,stop by coastingP2.12.8.2 Eart fault currentlimit 0,0 100,0 % 50,0 1333Table 6-33.Earth fault protection6.12.9 Cooling protectionCode Parameter Min Max Unit Default Cust ID NoteP2.12.9.1 Cooling FaultResponse 1 2 2 7620= No Action, Warning1= Warning, Warning2= Warning, Fault3= No Action, FaultP2.12.9.2 Cooling Fault delay 0,00 7,00 s 2,00 751Table 6-34.Cooling protection6.12.10 Fieldbus protectionCode Parameter Min Max Unit Default Cust ID NoteP2.12.10.1FieldbusCommunicationresponse0 5 2 7330=No Action1=Warning2= Fault3= Fault,stop by coasting4=Warning; Prev Freq5=Quick StopP2.12.10.2 FB Fault Delay 0,00 60,00 s 0,50 1850 Delay to fault when FBResponse is 4P2.12.10.3 FB Watchdog Delay 0,00 30,00 s 0,00 1354 Delay when WD pulse ismissing. 0,00 s = DisabledTable 6-35. Fieldbus protection