68 • Vacon apfiff09 marineTel. +35856.13 Fieldbus parametersCode Parameter Min Max Unit Default Cust ID NoteP2.13.1 Fieldbus min scale 0,00 320,00 Hz 0,00 850P2.13.2 Fieldbus max scale 0,00 320,00 Hz 0,00 851P2.13.3 Fieldbus processdata out 1 selection 0 10000 1 852Choose monitoring datawith parameter IDDef: Output FrequencyP2.13.4 Fieldbus processdata out 2 selection 0 10000 2 853 Def: Motor SpeedP2.13.5 Fieldbus processdata out 3 selection 0 10000 3 854 Def: Motor Current to FBP2.13.6 Fieldbus processdata out 4 selection 0 10000 4 855 Def: Motor TorqueP2.13.7 Fieldbus processdata out 5 selection 0 10000 5 856 Def: Motor PowerP2.13.8 Fieldbus processdata out 6 selection 0 10000 6 857 Def: Motor VoltageP2.13.9 Fieldbus processdata out 7 selection 0 10000 7 858 Def: DC-Link VoltageP2.13.10 Fieldbus processdata out 8 selection 0 10000 37 859 Def: Last Active FaultP2.13.11 Fieldbus processdata in 1 selection 0 10000 1140 876Choose controlled data withparameter ID.Def: FB Torque ReferenceP2.13.12 Fieldbus processdata in 2 selection 0 10000 46 877 Def: FB Limit ScalingP2.13.13 Fieldbus processdata in 3 selection 0 10000 47 878 Def: FB Adjust ReferenceP2.13.14 Fieldbus processdata in 4 selection 0 10000 48 879 Def: FB Analogue Output.P2.13.15 Fieldbus processdata in 5 selection 0 10000 0 880 Choose controlled data withparameter IDP2.13.16 Fieldbus processdata in 6 selection 0 10000 0 881 Choose controlled data withparameter IDP2.13.17 Fieldbus processdata in 7 selection 0 10000 0 882 Choose controlled data withparameter IDP2.13.18 Fieldbus processdata in 8 selection 0 10000 0 883 Choose controlled data withparameter IDP2.13.19 General Status WordID 0 10000 67 897 Choose monitoring data inGeneral Status WordP2.13.20 FB Actual SpeedMode 0 1 0 1741 0=Calculated 1=ActualP2.13.21 Control Slot Selector 0 8 0 1440 0=All 4=Slot D5=Slot EP2.13.22 State Machine 1 2 1 896 1 = Standard2 = ProfiDriveP2.13.23 FB Custom Minimum -32000 +32000 0 898 FB Speed ReferenceMinimum scalingP2.13.24 FB CustomMaximum -32000 +32000 +10000 899 FB Speed RederenceMaximum ScalingTable 6-36. Fieldbus parameters